Status Report Fields
The meaning of the above variables are:
APC is the header record indicating the STATUS format revision level,
the numberof records that follow the APC statement, and the number
of bytes that follow the record.
DATE is the date and time that the information was last obtained from
the UPS.
HOSTNAME is the name of the machine that collected the UPS data.
RELEASE is the apcupsd release number.
CABLE is the cable as specified in the configuration file.
MODEL is the UPS model as derived from information from the UPS.
UPSMODE is the mode in which apcupsd is operating.
STARTTIMEis the time/date that apcupsd was started.
UPSNAME is the name of the UPS as stored in the EEPROM.
STATUSis the current status of the UPS (ONLINE, CHARGING, ON-
BATT,...)
MASTERUPD is the last time the master sent an update to the slave.
This value is present only in slaveconfigurations.
LINEV is the current line voltage as returned by the UPS.
LOADPCT is the percentage of load capacity as estimated by the UPS.
BCHARGE is the percentage charge on the batteries.
TIMELEFT is the remaining runtime left on batteries as estimated by
the UPS.
MBATTCHGif the battery charge p ercentage (BCHARGE)drops b elow
this value, apcupsd will shutdown your system.
MINTIMEL apcupsd will shutdownyour system if theremaining runtime
equals or is below this point.
MAXTIME apcupsd will shutdown your system if the time on batteries
exceeds this value. A value of zero disables the feature.