5.4 Internal FM Mode
Introduction
Internal FM mode generates
Internal FM Mode Parameters
The Internal FM mode has the following front panel display:
|
|
| Int FM: 1,000 Hz | Pk dev: 10,000 Hz |
|
|
1 |
|
|
|
| ||
|
|
| ||||
3 |
|
| 1,000,000.00 Hz |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
Figure 5.4-1: Internal FM mode display
1. Modulating Frequency
2
4
In this field enter the frequency of the modulating sinusoid. You may enter from 0 Hz to 10,000 Hz in 1 Hz steps.
2. Peak Frequency Deviation
In this field specify the degree to which the modulating signal is allowed to change the carrier frequency. You may enter from 0 Hz (no change) to 5.0 MHz in 1 Hz steps
This parameter is a peak value. If the deviation were 1 KHz and the carrier frequency were 1 MHz, for example, then the output frequency will swing between a maximum of 1 MHz + 1 KHz and a minimum of 1 MHz - 1 KHz.
NOTE: If values for the deviation and carrier frequencies are entered such that the output frequency exceeds the 0 to 31.5 MHz range, distortion of the output waveform may result.
3. Carrier Frequency
In this field enter the frequency of the carrier. You may enter from 0 Hz (DC) to 31.5 MHz in 0.01 Hz steps.
NOTE: If values for the deviation and carrier frequencies are entered such that the output frequency exceeds the 0 to 31.5 MHz range, distortion of the output waveform may result.
4. Level
In this field enter the output level, from 4
NOTE: The level specified is a 50O loaded level. This is the level of the signal, which will appear across a 50O load connected to the SIG Out connector. Into an open circuit, the output swing will be twice the value entered.
Offset
You can enter an offset voltage for the output signal. For more information on output offsets refer to section 4.4.
Ext Gating Input
This TTL compatible input can be used to gate the output signal on or off. A logic high voltage turns off the output. For further information on the Ext Gating Input, refer to section 2.0.
16
BK Precision 4071 User Manual Rev.2.2