Page 10 | BRADFORD WHITE CORP. |
|
|
|
|
|
|
U.S. Installations (see note 1) | Canadian Installations (see note 2) |
A = Clearance above grade, veranda, porch, 12 inches (30 cm) | 12 inches (30 cm) |
deck, or balcony |
|
B = Clearance to window or door that may be opened
4 feet (1.2 m) below or to side of opening; | 36 inches (91 cm) |
1 foot (30 cm) above opening |
|
C = | Clearance to permanently closed window | See note 4 | See note 5 |
D = | Vertical clearance to ventilated soffit located |
|
|
| above the terminal within a horizontal | See note 4 | See note 5 |
| distance of 2 feet (61cm) from the center |
|
|
| line of the terminal |
|
|
E = | Clearance to unventilated soffit | See note 4 | See note 5 |
F = | Clearance to outside corner | See note 4 | See note 5 |
G = | Clearance to inside corner | See note 4 | See note 5 |
H = | Clearance to each side of center line |
| 3 feet (91 cm) within a height 15 feet above |
| extended above meter/regulator assembly | See note 4 | the meter/regulator assembly |
I = | Clearance to service regulator vent outlet | See note 4 | 3 feet (91 cm) |
J = | Clearance to nonmechanical air supply inlet |
|
|
| to building or the combustion air inlet to | 4 feet (1.2 m) below or to side of opening; | 36 inches (91 cm) |
| any other appliance | 1 foot (30 cm) above opening |
|
K = | Clearance to a mechanical air supply inlet | 3 feet (91 cm) above if within 10 feet (3 m) | 6 feet (1.83 m) |
|
| horizontally |
|
|
|
| Vent termination not allowed in this location |
L = |
| Vent termination not allowed in this location | for category IV appliances. A vent shall not |
Clearance above paved sidewalk or paved | for category IV appliances. For Category III | terminate directly above a sidewalk or paved | |
| driveway located on public property | appliances, vent must terminate at least 7 | driveway that is located between two single |
|
| feet (2.13m) above the sidewalk or driveway. | family dwellings and serves both dwellings. |
|
|
| For Category III appliances that do not violate |
|
|
| the previous condition, vent must terminate |
|
|
| at least 7 feet (2.13m) above the sidewalk or |
|
|
| driveway. |
M = Clearance under veranda, porch, deck, | See note 4 | 12 inches (30 cm) (see note 3) | |
| or balcony |
|
|
Notes:
1.In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2.In accordance with the current
3.Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4.For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5.For clearances not specified in