Page 5
COPPER BRUTE II (500 - 2000)
Model Character Designation
1-3 Model Series Designation
B W C = Bradfrod White, Copper Brute II
4 Usage
H = Hydronic
V = Volume Water
5-8 Size
0 5 0 0 = 500,000 BTU/h input
0 7 5 0 = 750,000 BTU/h input
1 0 0 0 = 999,000 BTU/h input
1 2 5 0 = 1,250,000 BTU/h input
1 5 0 0 = 1,500,000 BTU/h input
1 7 5 0 = 1,750,000 BTU/h input
2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas
P = Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
K = Two-stage (models 500 & 750)
N = Three-stage (model 1000)
L = Four-stage (models 1250 - 2000)
13 Revision
2 = Second version
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. BWCV)
C = Glass-lined cast iron / copper (standard BWCH)
K = Bronze / copper
N = Glass-lined cast iron / cu-nickel
P = Glass-lined cast iron / cu-nickel / brz trim
S = Bronze / cu-nickel
15 Option Code
X = Standard unit
J = CSD-1, FM, IRI, IL
L = MN and LDS (Indoor units only)
16 Pump Options
X = No Pump
H = Pump mounted, hard water pump
N = Pump mounted, normal pump
S = Pump mounted, soft water pump
1.3 Warranty
Bradford White, Copper Brute II appliances
are covered by a limited warranty. The owner should
ll out the warranty registration card and return it to
Bradford White.
All warranty claims must be made to an
authorized Bradford White representative or directly
to the factory. Claims must include the serial number
and model (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figure 1.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower oors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certied by CSA-
International for installation on combustible ooring;
in basements; in closets, utility rooms or alcoves.
Copper Brute II Boilers or Water Heaters must
never be installed on carpeting. The location for the
appliance should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
control replacement, etc.). When vented vertically, the
Copper Brute II must be located as close as practical
to a chimney or outside wall. If the vent terminal and/
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the
local area, both terminals should be installed at an
appropriate level above grade.
The dimensions and requirements that are shown
in Table 1 should be met when choosing the locations
for the appliance.
REQUIRED RECOMMENDED