COPPER BRUTE II (500 - 2000) | Page 19 |
|
|
|
|
SYSTEM
RETURN
C
B
A
PUMP LOCATION FOR
T1
COLD WATER
| SYSTEM |
SYSTEM PUMP | SUPPLY |
|
ADJUSTMENT PROCEDURE TO MAINTAIN
B | 120°F INLET TEMP: |
|
A1. Turn on boiler and open valves A & B.
2.After
3.If T1 is greater than 120°F, slowly close valve A until T1 drops to 120°F.
4.Check after system operating temperature has stabilized. Make final adjustments.
T1
CAUTION: THIS DRAWING SHOWS SUGGESTED |
|
| |||
PIPING CONFIGURATION AND VALVING, CHECK | PUMP LOCATION FOR | ||||
WITH LOCAL CODES AND ORDINANCES FOR | |||||
|
| ||||
ADDITIONAL REQUIREMENTS. |
|
| PRIMARY/SECONDARY MANDITORY FOR ALL | ||
|
|
|
| ||
|
|
|
| VARIABLE FLOW SYSTEMS | |
LEGEND |
|
| INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM | ||
|
| PIPING & SIZING OF EXPANSION TANK | |||
|
|
|
| ||
THERMOMETER |
| EXPANSION TANK | PER TANK MANUFACTURER'S INSTRUCTIONS | ||
|
| ||||
| WITH AIR SCOOP AND | DIMENSION "C" (COMMON PIPING) TO BE FOUR | |||
|
| ||||
|
| AUTO AIR VENT | PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES) | ||
| PURGE |
|
| ||
TEMPERATURE |
|
|
| ||
VALVE |
|
| BOILER CIRCUIT PIPING MUST BE EQUAL | ||
SENSOR |
|
| |||
|
|
|
| TO BOILER WATER CONNECTION SIZE | |
GLOBE VALVE |
| BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER | |||
|
|
| |||
|
|
|
| ||
CHECK VALVE |
| VALVE |
| DOTTED DEVICES INDICATE ALTERNATE LOCATIONS | |
|
|
| |||
|
|
|
| ||
|
|
|
| PUT BOILER CONTROL SENSOR IN THE SYSTEM | |
PRESSURE REDUCING VALVE |
|
| SUPPLY WHEN USING THIS PIPING STYLE. | ||
|
|
| |||
W/ FAST FILL BYPASS | PUMP |
| MINIMUM BOILER INLET WATER TEMPERATURE | ||
|
|
|
|
MUST BE AT LEAST 120°F.