Page 4 BRADFORD WHITE CORP.
SECTION 1.General Information
USING THIS MANUAL – Because the
Copper Brute II Boilers and Copper Brute II Water
Heaters are identical appliances, with the exception
of materials of manufacture, labels and ultimate
use application, this manual provides information
for the proper installation, operation and
maintenance of both products. Where differences
exist between the application of the appliances and
their operation, the sections pertinent to only one
appliance or the other will be so identied.
In the Commonwealth of Massachusetts, this
appliance must be installed by a licensed plumber or
gas tter.
WARNING
The Copper Brute II hydronic, boiler or water
heater must be installed in accordance with the
procedures detailed in this manual, or the Bradford
White warranty may be voided. The installation must
conform to the requirements of the local jurisdiction
having authority, and, in the United States, to the
latest edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA54. In Canada, the installation must
conform to the latest edition of the Natural Gas
and Propane Installation Code, CSA B149.1 and/
or local codes. Where required by the authority
having jurisdiction, the installation of Copper Brute
II appliances must conform to the Standard for
Controls and Safety Devices for Automatically Fired
Boilers, ANSI/ASME CSD-1. Any modications to
the boiler, its gas controls, or wiring may void the
warranty. If eld conditions require modications,
consult the factory representative before initiating
such modications.

1.1 Introduction

This manual provides information necessary
for the installation, operation, and maintenance of
Bradford White Corp, Copper Brute II copper tube
appliances. Read it carefully before installation.
All application and installation procedures
should be reviewed completely before proceeding
with the installation. Consult the Bradford White
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Copper Brute II appliance is protected
against over pressurization. A pressure relief valve
is tted to all appliances. It is installed on the outlet
header, at the water outlet of the appliance.
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13" w.c. (3.2kPa).
All installations must be made in accordance with:
1) In the U.S., the " National Fuel Gas
Code"ANSI Z223.1/NFPA54, Latest Edition and all
applicable local codes as required by the Authorities
Having Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code"
(NEC), ANSI/NFPA 70, latest Edition and all
applicable local codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code
- Part 1”, CSA STD. C22.1 and all applicable local
codes as required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.

1.2 Model Identication

Consult the rating plate on the unit. The
following information describes the model number
structure.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B W C A C 2
SERIES
B W C
USAGE
H
V
SIZE
0 5 0 0
0 7 5 0
1 0 0 0
1 2 5 0
1 5 0 0
1 7 5 0
2 0 0 0
FUEL
N
P
ALTITUDE
A
FIRING
MODE
K (500/750)
N (1000)
L (1250-2000)
LOCATION
C
REVISION
2
HEAT
EXCHANGER
B
C
K
N
P
S
OPTIONS
CODE
X
J
L
PUMP
OPTIONS
X
H
N
S