TTW1 Universal Service

Replacement Blower

M1TW Series

Disconnect (2) flag terminals and tubing

Step 7.from pressure switch to remove.

b.) Replace the current pressure switch ONLY IF the model is for high altitude (2001 ft. & above).

Warning:

Failure to replace universal blower pressure

 

switch for high altitude will result in improper

 

water heater operation.

 

 

 

i. For high altitude applications, the

 

factory installed pressure switch

 

must be replaced. The correct

 

pressure switch is P/N

 

239-47192-01 with a setting of

 

-0.70" wc.

 

c.) When installing the high altitude

 

pressure switch, be sure to reconnect

 

the pressure switch tubing to both the

 

pressure tap and the switch itself.

 

Also, reconnect the wires for the

 

pressure switch circuit to the new

 

pressure switch. Ensure that

 

the tubing is not kinked.

Step 8.

a.) Ensure that once in place, the pressure

 

switch should be mounted such that its

 

diaphragm is in the vertical position.

Choose corresponding pressure switch from kit. Verify correct P/N and setting on label to match this model’s requirements, as shown in Step 7b.

Be sure to reconnect

tubing and (2) flag

terminals.

Verify electrical

 

and tubing

Mount in vertical

connections.

position using

 

bracket.