PERFORMANCE DATA (cont)

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

581B060 (5 TONS)

Temp (F)

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

Air Ent

 

1500/0.08

 

 

1750/0.09

 

 

2000/0.11

 

 

 

2500/0.13

 

Condenser

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

 

67

62

72

67

 

62

72

67

62

 

 

 

 

 

 

 

 

TC

70.8

65.4

58.5

72.5

 

67.3

61.1

73.0

68.4

 

62.8

74.8

70.3

64.8

75

 

SHC

34.1

42.7

49.9

35.7

 

45.5

54.2

36.8

48.0

 

57.8

39.6

53.0

63.4

 

 

kW

3.53

3.49

3.44

3.55

 

3.50

3.46

3.55

3.51

 

3.47

3.57

3.54

3.48

 

 

TC

68.9

63.2

55.3

70.5

 

65.1

57.9

72.2

66.4

 

60.2

73.2

68.1

62.9

85

 

SHC

33.5

41.8

48.4

35.0

 

44.8

52.8

37.0

47.6

 

56.8

39.3

52.5

62.4

 

 

kW

3.98

3.94

3.87

4.00

 

3.96

3.90

4.03

3.97

 

3.92

4.04

3.99

3.94

95

 

TC

66.8

60.6

52.4

68.3

 

62.5

54.3

69.3

63.8

 

56.6

71.2

65.6

60.6

 

SHC

32.8

40.7

47.0

34.5

 

43.8

51.1

36.0

46.7

 

55.0

39.1

51.8

60.5

 

 

kW

4.48

4.43

4.35

4.50

 

4.45

4.37

4.51

4.46

 

4.40

4.55

4.48

4.44

 

 

TC

64.3

57.7

49.9

65.9

 

59.8

51.7

66.9

61.1

 

54.1

68.4

62.8

58.4

105

 

SHC

32.0

39.6

45.8

33.7

 

42.8

49.7

35.3

45.7

 

53.5

38.4

51.0

58.4

 

 

kW

5.03

4.96

4.87

5.05

 

4.99

4.90

5.06

5.00

 

4.93

5.08

5.02

4.98

 

 

TC

61.5

54.8

47.3

62.8

 

56.7

49.1

64.0

58.2

 

51.6

65.4

59.9

56.1

115

 

SHC

31.0

38.4

44.5

32.5

 

41.6

48.2

34.4

44.6

 

51.6

37.4

50.0

56.1

 

 

kW

5.61

5.55

5.46

5.62

 

5.58

5.49

5.65

5.60

 

5.52

5.67

5.61

5.57

 

 

TC

58.7

51.6

44.5

59.9

 

53.4

46.2

60.8

54.9

 

49.0

62.2

56.8

53.5

125

 

SHC

30.0

37.2

43.1

31.7

 

40.4

46.2

33.3

43.4

 

48.9

36.4

48.9

53.4

 

 

kW

6.27

6.19

6.09

6.28

 

6.21

6.13

6.29

6.24

 

6.17

6.31

6.27

6.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B072 (6 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

Air Ent

 

1800/0.05

 

 

2100/0.06

 

 

2400/0.06

 

 

 

3000/0.08

 

Condenser

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

 

67

62

72

67

 

62

72

67

62

 

 

 

 

 

 

 

 

TC

86.7

80.7

74.4

88.8

 

82.7

76.6

90.5

84.4

 

78.2

92.6

86.3

81.0

75

 

SHC

43.0

53.7

63.8

45.0

 

57.4

68.9

47.2

61.2

 

73.6

51.2

67.4

80.7

 

 

kW

4.58

4.46

4.33

4.63

 

4.50

4.38

4.67

4.55

 

4.41

4.72

4.58

4.47

 

 

TC

84.1

78.2

72.0

86.4

 

80.3

74.1

88.2

81.7

 

75.7

90.2

84.0

78.8

85

 

SHC

42.0

52.6

62.7

44.5

 

56.6

68.0

46.8

60.2

 

72.5

50.6

67.4

78.7

 

 

kW

5.10

4.97

4.85

5.16

 

5.03

4.90

5.21

5.06

 

4.93

5.26

5.12

4.99

95

 

TC

81.3

75.3

69.2

83.4

 

77.3

71.3

85.1

78.9

 

72.9

87.2

80.6

76.2

 

SHC

41.0

51.4

61.4

43.4

 

55.3

66.6

45.8

59.2

 

71.2

50.2

65.8

76.2

 

 

kW

5.65

5.52

5.39

5.71

 

5.57

5.44

5.77

5.62

 

5.48

5.83

5.66

5.55

 

 

TC

77.9

72.0

66.1

80.0

 

73.8

68.0

81.6

75.3

 

69.6

83.4

77.1

73.2

105

 

SHC

39.7

50.2

60.0

42.2

 

54.0

65.2

44.6

57.8

 

69.3

49.0

64.5

73.2

 

 

kW

6.22

6.08

5.94

6.29

 

6.13

6.00

6.34

6.17

 

6.04

6.40

6.22

6.12

 

 

TC

74.7

68.4

61.8

75.9

 

70.0

64.1

77.6

71.3

 

66.5

78.7

73.0

70.1

115

 

SHC

38.7

48.8

58.1

40.8

 

52.6

63.2

43.3

56.4

 

66.4

46.9

63.2

70.0

 

 

kW

6.84

6.68

6.49

6.87

 

6.71

6.56

6.93

6.75

 

6.63

6.96

6.80

6.72

 

 

TC

70.3

63.6

57.2

71.8

 

65.5

59.1

72.9

66.8

 

61.9

74.0

68.6

66.4

125

 

SHC

37.2

47.0

55.8

39.5

 

51.0

59.1

41.7

55.0

 

61.9

45.4

61.8

66.3

 

 

kW

7.43

7.25

7.03

7.48

 

7.30

7.13

7.51

7.35

 

7.22

7.54

7.41

7.33

COOLING CAPACITIES (cont) Standard Ratings

LEGEND

BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb

kW — Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb = tedb

sensible heat capacity (Btuh)

1.10 x cfm

 

tlwb = wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where hewb = Enthalpy of air entering indoor coil.

3.The SHC is based on 80 F edb temperature of air entering evap- orator coil.

Below 80 F db, subtract (corr factor x cfm) from SHC. Above 80 F db, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (db – 80).

19

Page 19
Image 19
Bryant 581B manual PERFORMANCE DATA cont, COOLING CAPACITIES cont