Bryant 581B manual PERFORMANCE DATA cont, 69.9

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 23
Image 23
69.9

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont)

581B060 (5 TONS)

Temp (F)

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

Air Ent

 

1500/0.08

 

 

1750/0.09

 

 

2000/0.11

 

 

 

2500/0.13

 

Condenser

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

 

67

62

72

67

 

62

72

67

62

 

 

 

 

 

 

75

 

TC

69.9

62.7

56.2

74.7

 

67.3

61.0

78.5

71.2

 

64.8

81.7

75.5

69.3

 

SHC

29.0

36.9

43.9

31.7

 

40.5

51.2

34.5

44.2

 

55.4

37.8

52.0

62.8

 

 

kW

3.61

3.55

3.51

3.64

 

3.58

3.49

3.65

3.60

 

3.51

3.62

3.58

3.51

85

 

TC

65.9

59.1

51.7

70.6

 

63.2

56.3

75.5

66.8

 

60.7

78.1

70.8

65.1

 

SHC

25.3

34.0

41.9

27.5

 

37.6

48.0

30.7

41.6

 

52.0

33.8

47.4

58.0

 

 

kW

4.05

3.97

3.91

4.07

 

4.01

3.92

4.11

4.00

 

3.95

4.08

4.02

3.96

95

 

TC

61.9

55.2

47.7

66.5

 

58.8

51.3

70.4

61.9

 

55.7

74.2

65.9

60.6

 

SHC

21.6

31.1

40.0

23.5

 

34.5

44.6

26.0

38.6

 

47.9

30.0

42.8

52.6

 

 

kW

4.53

4.43

4.35

4.55

 

4.47

4.37

4.56

4.42

 

4.41

4.58

4.49

4.44

105

 

TC

57.7

51.1

44.9

61.8

 

54.5

47.7

65.1

57.2

 

50.8

68.4

60.3

56.1

 

SHC

18.1

27.8

35.7

20.0

 

31.2

40.1

22.1

34.3

 

43.5

26.1

38.9

48.5

 

 

kW

5.05

4.93

4.84

5.09

 

4.97

4.88

5.11

4.96

 

4.92

5.11

5.03

4.98

115

 

TC

53.4

47.2

42.0

56.6

 

50.0

44.2

59.6

52.5

 

46.2

62.6

54.9

51.6

 

SHC

14.7

24.6

31.5

16.5

 

27.8

35.7

18.2

30.0

 

39.0

22.1

34.9

44.3

 

 

kW

5.60

5.49

5.40

5.64

 

5.52

5.45

5.69

5.55

 

5.48

5.69

5.61

5.57

125

 

TC

48.7

42.0

36.9

51.3

 

45.0

39.0

54.1

46.8

 

40.9

56.9

49.2

45.9

 

SHC

10.9

19.6

28.0

12.5

 

22.2

31.5

13.5

24.0

 

34.0

16.5

28.0

38.8

 

 

kW

6.26

6.12

6.02

6.28

 

6.18

6.09

6.33

6.18

 

6.13

6.33

6.27

6.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B072 (6 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

Air Ent

 

1800/0.05

 

 

2100/0.06

 

 

2400/0.06

 

 

 

3000/0.08

 

Condenser

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

 

67

62

72

67

 

62

72

67

62

 

 

 

 

 

 

75

 

TC

82.6

75.6

68.5

84.9

 

78.0

70.9

85.9

79.5

 

73.5

89.1

82.7

77.0

 

SHC

36.0

44.8

55.4

37.5

 

49.1

59.7

38.8

51.1

 

64.0

41.8

58.1

70.2

 

 

kW

4.60

4.52

4.36

4.67

 

4.57

4.46

4.70

4.57

 

4.45

4.77

4.61

4.51

85

 

TC

78.2

71.6

64.5

80.9

 

73.4

65.8

82.0

74.4

 

67.9

85.8

78.2

72.3

 

SHC

31.4

41.2

51.7

33.0

 

44.7

55.8

34.7

47.4

 

60.1

37.6

54.3

66.7

 

 

kW

5.16

5.03

4.89

5.22

 

5.11

4.96

5.26

5.09

 

4.97

5.32

5.17

5.04

95

 

TC

73.8

67.4

60.2

76.3

 

68.3

60.5

77.5

69.3

 

62.3

82.0

72.8

67.5

 

SHC

27.0

37.6

47.9

28.2

 

40.0

51.6

30.2

43.7

 

56.2

33.6

49.2

62.9

 

 

kW

5.75

5.60

5.44

5.80

 

5.66

5.48

5.84

5.68

 

5.53

5.90

5.73

5.60

105

 

TC

68.4

62.6

55.9

71.4

 

64.3

56.2

72.1

64.6

 

58.3

75.7

67.0

62.4

 

SHC

22.3

33.5

43.5

23.4

 

36.5

48.0

25.4

38.4

 

50.2

29.1

45.2

56.2

 

 

kW

6.37

6.22

6.06

6.45

 

6.27

6.10

6.46

6.29

 

6.16

6.53

6.36

6.24

115

 

TC

63.4

57.8

50.7

66.0

 

60.1

51.5

66.4

59.6

 

54.5

68.8

60.8

57.5

 

SHC

18.1

29.5

38.9

18.8

 

32.9

44.1

20.7

33.3

 

43.8

24.3

41.4

49.7

 

 

kW

7.04

6.89

6.68

7.10

 

6.91

6.74

7.12

6.95

 

6.83

7.16

7.01

6.92

125

 

TC

55.5

49.6

45.8

58.4

 

52.4

46.1

57.6

52.1

 

49.5

59.2

52.8

53.1

 

SHC

15.3

24.0

35.2

15.7

 

27.5

39.0

17.5

27.5

 

38.4

20.9

34.6

44.4

 

 

kW

7.80

7.61

7.38

7.83

 

7.67

7.49

7.89

7.72

 

7.58

7.92

7.78

7.70

LEGEND

BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb

kW — Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb

= tedb

 

sensible capacity (Btuh)

 

 

1.10 x cfm

 

 

 

 

tlwb

= Wet-bulb temperature corresponding to enthalpy of air

 

leaving evaporator coil (hlwb)

hlwb

= hewb

 

total capacity (Btuh)

 

 

4.5 x cfm

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil.

3.The SHC is based on 80 F edb temperature of air entering evapo- rator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).

23

Page 23
Image 23
Bryant 581B manual PERFORMANCE DATA cont, 69.9