Bryant 581B Ari* Capacities, Heating Capacities And Efficiencies, Sizes 036-120OnlySize 150 Only

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 5
Image 5
ARI* CAPACITIES

ARI* CAPACITIES

UNIT

NOMINAL

STANDARD

COOLING

TOTAL

SEER†

EER

SOUND RATING

IPLV**

581B

TONS

CFM

(Btuh)

kW

(dB)

 

 

 

036

3

1200

36,000

3.21

13.00

11.20

76

048

4

1450

47,000

4.25

13.00

11.05

76

060

5

1750

60,000

5.55

13.00

11.00

80

072

6

2100

74,000

6.70

11.00

80

090

71/2

3000

90,000

8.18

11.00

82

11.6

102

81/2

3000

102,000

9.44

10.80

82

10.9

120

10

3200

120,000

10.91

11.00

84

9.7

150

121/2

4300

140,000

14.04

9.50

86

9.8

LEGEND

dB — Decibels

EER — Energy Efficiency Ratio

IPLV — Integrated Part-Load Value

SEER — Seasonal Energy Efficiency Ratio

*Air-Conditioning & Refrigeration Institute.

†Applies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units.

NOTES:

1.Rated in accordance with ARI Standard 210/240 (size 036-120 units) or 360 (size 150 units) and 270 (size 036-150 units).

2.Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:

Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db outdoor entering-air temperature.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

Sizes 036-120 OnlySize 150 Only

HEATING CAPACITIES AND EFFICIENCIES

SIZE

HEATING INPUT (Btuh)

OUTPUT CAPACITY

TEMPERATURE

AFUE

STEADY-STAGE

581B

Stage 2/Stage 1

(Btuh)

RISE

(%)

EFFICIENCY (%)

036071*

—/

72,000

—/

59,040

15-45

82

82

036072†

72,000/ 50,000

59,040/

41,000

15-45

82

82

036114*

—/115,000

—/

92,000

55-85

80

80

036115†

115,000/ 82,000

92,000/

65,600

55-85

80

82

036060N**

—/

60,000

—/

50,000

20-50

81

81

036090N**

— 90,000

—/

74,000

30-60

81

81

048071*

—/

72,000

—/

59,040

15-45

82

82

048072†

72,000/ 50,000

59,040/

41,000

15-45

82

82

048114*

—/115,000

—/

92,000

35-65

81

81

048115†

115,000/ 82,000

93,150/

66,420

35-65

81

81

048149*

—/150,000

—/120,000

50-80

80

80

048150†

150,000/120,000

120,000/

96,000

50-80

80

80

048060N**

—/

60,000

—/

50,000

20-50

81

81

048090N**

—/

90,000

—/

74,000

30-60

81

81

048120N**

—/120,000

—/101,000

40-70

82

82

060071*

—/

72,000

—/

59,040

15-45

82

82

060072†

72,000/ 50,000

59,040/

41,000

15-45

82

82

060114*

—/115,000

—/

93,150

35-65

81

81

060115†

115,000/82,000

93,150/

66,420

35-65

81

81

060149*

—/150,000

—/120,000

50-80

80

80

060150†

150,000/120,000

120,000/

96,000

50-80

80

80

060060N**

—/

60,000

—/

50,000

20-50

81

81

060090N**

—/

90,000

—/

74,000

30-60

81

81

060120N**

—/120,000

—/101,000

40-70

82

82

072072

72,000/ 50,000

59,040/

41,000

15-45

82

82

072115

115,000/ 82,000

93,150/

66,420

35-65

81

81

072150

150,000/120,000

120,000/

96,000

50-80

80

80

090125

125,000/ 90,000

102,500/

72,900

20-50

82

82

090180

180,000/120,000

147,600/

98,400

35-65

82

82

090224

224,000/180,000

183,700/147,600

45-75

82

82

102125

125,000/ 90,000

102,500/

72,900

20-50

82

82

102180

180,000/120,000

147,600/

98,400

35-65

82

82

102224

224,000/180,000

183,700/147,600

45-75

82

82

120180

180,000/120,000

147,600/

98,400

35-65

82

82

120224

224,000/180,000

183,700/147,600

45-75

82

82

120250

250,000/200,000

200,000/160,000

40-70

80

80

150224

224,000/180,000

183,700/147,600

45-75

82

82

150250

250,000/200,000

200,000/160,000

40-70

80

80

LEGEND

AFUE — Annual Fuel Utilization Efficiency

*California rated three-phase models.

†Three-phase standard models have heating input values as shown. Single-phase standard models have one-stage heating with heating input values as follows:

581BJV036-060072, 72,000 Btuh

581BJV036-060115, 115,000 Btuh

581BJV048-060150, 150,000 Btuh

**California SCAQMD compliant Low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

5

Page 5
Image 5