PERFORMANCE DATA (cont)
581B FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR
STANDARD MOTOR
Unit |
|
|
|
|
| Motor Pulley Turns Open |
|
|
|
|
| ||||
581B |
| 0 | 1/2 | 1 | 11/2 | 2 | 21/2 | 3 | 31/2 | 4 | 41/2 | 5 | 51/2 | 6 | |
036 |
| 1090 | 1055 | 1025 | 990 | 960 | 925 | 890 | 860 | 825 | 795 | 760 | — | — | |
048 |
| 1185 | 1150 | 1115 | 1080 | 1045 | 1015 | 980 | 945 | 910 | 875 | 840 | — | — | |
060 |
| 1460 | 1425 | 1385 | 1350 | 1315 | 1275 | 1240 | 1205 | 1165 | 1130 | 1095 | 1055 | 1020 | |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
060 | 1585 | 1540 | 1490 | 1445 | 1400 | 1350 | 1305 | 1260 | 1210 | 1165 | 1120 | — | — | ||
and 072 | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
090,102 |
| 1085 | 1060 | 1035 | 1010 | 985 | 960 | 935 | 910 | 890 | 865 | 840 | — | — | |
120 |
| 1080 | 1060 | 1035 | 1015 | 990 | 970 | 950 | 930 | 905 | 885 | 860 | — | — | |
150 |
| 1260 | 1220 | 1185 | 1155 | 1130 | 1100 | 1075 | 1045 | 1015 | 990 | 960 | 930 | 900 |
581B FAN RPM AT MOTOR PULLEY SETTING WITH
Unit |
|
|
|
|
| Motor Pulley Turns Open |
|
|
|
|
| ||
581B | 0 | 1/2 | 1 | 11/2 | 2 | 21/2 | 3 | 31/2 | 4 | 41/2 | 5 | 51/2 | 6 |
036 | 1455 | 1423 | 1392 | 1360 | 1328 | 1297 | 1265 | 1233 | 1202 | 1170 | 1138 | 1107 | 1075 |
048 | 1455 | 1423 | 1392 | 1360 | 1328 | 1297 | 1265 | 1233 | 1202 | 1170 | 1138 | 1107 | 1075 |
060 | 1685 | 1589 | 1557 | 1525 | 1493 | 1460 | 1428 | 1396 | 1364 | 1332 | 1300 | — | — |
072 | 1685 | 1589 | 1557 | 1525 | 1493 | 1460 | 1428 | 1396 | 1364 | 1332 | 1300 | — | — |
090 | 1080 | 1025 | 1007 | 988 | 970 | 952 | 933 | 915 | 897 | 878 | 860 | — | — |
102 | 1080 | 1025 | 1007 | 988 | 970 | 952 | 933 | 915 | 897 | 878 | 860 | — | — |
120 | 1130 | 1112 | 1087 | 1062 | 1037 | 1212 | 987 | 962 | 937 | 912 | 887 | 962 | 830 |
EVAPORATOR-FAN MOTOR DATA — STANDARD MOTOR
UNIT | UNIT | MAXIMUM | MAXIMUM | UNIT VOLTAGE | MAXIMUM | |
581B | PHASE | CONTINUOUS BHP* | OPERATING WATTS* | AMP DRAW | ||
| ||||||
| Single | 1.20 | 1000 | 208/230 | 4.9 | |
036 |
|
|
| 208/230 | 4.9 | |
Three | 1.20 | 1000 | 460 | 2.2 | ||
| ||||||
|
|
|
| 575 | 2.2 | |
| Single | 1.20 | 1000 | 208/230 | 4.9 | |
048 |
|
|
| 208/230 | 4.9 | |
Three | 1.20 | 1000 | 460 | 2.2 | ||
| ||||||
|
|
|
| 575 | 2.2 | |
| Single | 1.30 | 1650 | 208/230 | 10.1 | |
060 |
|
|
| 208/230 | 6.7 | |
Three | 2.40 | 2120 | 460 | 3.0 | ||
| ||||||
|
|
|
| 575 | 3.0 | |
|
|
|
| 208/230 | 6.7 | |
072 | Three | 2.40 | 2120 | 460 | 3.0 | |
|
|
|
| 575 | 3.0 | |
|
|
|
| 208/230 | 8.6 | |
090,102 | Three | 2.90 | 2615 | 460 | 3.9 | |
|
|
|
| 575 | 3.9 | |
|
|
|
| 208/230 | 12.2 | |
120 | Three | 3.70 | 3775 | 460 | 5.5 | |
|
|
|
| 575 | 5.5 | |
|
|
|
| 208/230 | 17.3 | |
150 | Three | 5.25 | 4400 | 460 | 8.5 | |
|
|
|
| 575 | 8.5 |
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with con- fidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.