PERFORMANCE DATA (cont)

ALTITUDE COMPENSATION*

ALTITUDE COMPENSATION*

581B036-072

581B090-150

 

72,000 AND 115,000/

 

 

 

60,000 and 90,000

150,000/120,000 BTUH

ELEVATIO

BTUH NOMINAL

NOMINAL INPUT

INPUT*

 

 

N

 

 

(ft)

Natural

Liquid

Natural

Liquid

Gas

Propane

Gas

Propane

 

 

Orifice

Orifice

Orifice

Orifice

 

Size†

Size†

Size†

Size†

0-2,000

33/38

43/45

30/32

38/42

2,000

34/39

43/46

30/33

39/42

3,000

35/40

44/47

31/34

40/43

4,000

36/41

44/47

32/35

41/43

5,000

36/41

44/48

33/35

42/43

6,000

37/42

45/48

34/36

43/44

7,000

37/42

45/49

35/37

43/44

8,000

38/43

46/49

36/37

44/45

9,000

39/43

47/50

37/38

44/46

10,000

41/44

48/50

38/40

45/47

11,000

43/45

48/51

39/41

45/48

12,000

44/45

49/51

40/42

46/49

13,000

44/46

49/52

41/43

47/49

14,000

45/47

50/52

42/43

47/50

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your Bryant distributor.

 

125,000-224,000 BTUH

250,000 BTUH

ELEVATION

NOMINAL INPUT

NOMINAL INPUT

Natural

Liquid

Natural

Liquid

(ft)

Gas

Propane

Gas

Propane

 

Orifice

Orifice

Orifice

Orifice

 

Size†

Size†

Size†

Size†

0-2,000

31

41

30

38

2,000

32

42

30

39

3,000

32

42

31

40

4,000

32

42

32

41

5,000

33

43

33

42

6,000

34

43

34

43

7,000

35

44

35

43

8,000

36

44

36

44

9,000

37

45

37

44

10,000

38

46

38

45

11,000

39

47

39

45

12,000

40

47

40

46

13,000

41

48

41

47

14,000

42

48

42

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your local Bryant distributor.

ALTITUDE DERATING FACTOR*

581B036-150

ELEVATION

MAXIMUM HEATING VALUE

(Btu/ft3)

 

0-2000

1100

2001-3000

1050

3001-4000

1000

4001-5000

950

5001-6000

900

*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above sea level. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.