Bryant 581B manual PERFORMANCE DATA cont, FAN PERFORMANCE — VERTICAL DISCHARGE UNITS cont

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 27
Image 27
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

PERFORMANCE DATA (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

581B048 (4 TONS) — STANDARD MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

0.1

 

0.2

 

 

 

 

0.3

0.4

 

 

 

 

 

0.6

 

0.7

 

 

 

 

0.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

1200

596

 

0.20

 

665

 

0.25

 

722

 

0.31

779

 

0.36

 

872

 

0.48

 

915

 

0.54

 

957

 

0.60

 

1300

633

 

0.24

 

699

 

0.30

 

754

 

0.36

809

 

0.42

 

902

 

0.55

 

943

 

0.61

 

984

 

0.67

 

1400

672

 

0.30

 

735

 

0.36

 

788

 

0.42

840

 

0.48

 

933

 

0.62

 

972

 

0.69

 

1011

 

0.75

 

1500

711

 

0.35

 

770

 

0.42

 

822

 

0.49

873

 

0.55

 

963

 

0.69

 

1002

 

0.77

 

1041

 

0.84

 

1600

751

 

0.42

 

835

 

0.49

 

871

 

0.56

907

 

0.63

 

993

 

0.77

 

1033

 

0.85

 

1072

 

0.93

 

1700

791

 

0.49

 

873

 

0.57

 

907

 

0.65

941

 

0.72

 

1024

 

0.87

 

1064

 

0.96

 

1103

 

1.04

 

1800

831

 

0.58

 

881

 

0.66

 

929

 

0.74

976

 

0.81

 

1057

 

0.97

 

1095

 

1.06

 

1132

 

1.14

 

1900

872

 

0.67

 

919

 

0.75

 

965

 

0.84

1011

 

0.92

 

1091

 

1.08

 

1127

 

1.17

 

1162

 

1.25

 

2000

913

 

0.77

 

958

 

0.86

 

1002

 

0.95

1046

 

1.03

 

 

 

 

 

 

 

 

 

 

1195

 

1.38

 

 

1125

 

1.21

 

1160

 

1.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B048 (4 TONS) — STANDARD MOTOR (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

0.9

 

1.0

 

 

 

 

1.1

1.2

 

 

 

 

 

1.4

 

1.6

 

 

 

 

1.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

1200

993

 

0.65

 

1028

 

0.69

 

1056

 

0.72

1083

 

0.74

 

1134

 

0.80

 

1185

 

0.88

 

1231

 

0.99

 

1300

1021

 

0.74

 

1058

 

0.80

 

1090

 

0.85

1121

 

0.89

 

1171

 

0.94

 

1219

 

1.00

 

1268

 

1.10

 

1400

1049

 

0.82

 

1086

 

0.89

 

1120

 

0.96

1153

 

1.00

 

1210

 

1.12

 

1257

 

1.17

 

1307

 

1.25

 

1500

1077

 

0.92

 

1113

 

0.99

 

1147

 

1.06

1180

 

1.13

 

 

 

 

 

 

 

 

 

 

1339

 

1.43

 

 

 

 

1241

 

1.27

 

1295

 

1.37

 

 

1600

1107

 

1.00

 

1141

 

1.09

 

1174

 

1.17

 

 

 

 

 

1269

 

1.40

 

1326

 

1.54

 

1376

 

1.65

 

 

1207

 

1.25

 

 

 

 

 

1700

1137

 

1.12

 

1171

 

1.20

 

1203

 

1.29

1235

 

1.37

 

1296

 

1.53

 

1354

 

1.70

 

1407

 

1.84

 

1800

 

 

 

 

 

 

 

 

 

 

1233

 

1.41

1263

 

1.49

 

1323

 

1.67

 

1381

 

1.85

 

1436

 

2.02

 

1167

 

1.23

 

1202

 

1.32

 

 

 

 

 

 

1900

1197

 

1.35

 

1232

 

1.45

 

1263

 

1.54

1294

 

1.63

 

1351

 

1.81

 

1408

 

2.00

 

1463

 

2.19

 

2000

1229

 

1.48

 

1262

 

1.58

 

1294

 

1.68

1325

 

1.78

 

1362

 

1.97

 

1436

 

2.16

 

1489

 

2.36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B048 (4 TONS) — HIGH-STATIC MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

 

 

0.6

 

 

 

0.8

 

 

 

 

1.0

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

 

Bhp

 

Rpm

 

 

Bhp

Rpm

 

Bhp

 

 

 

Rpm

 

Bhp

Rpm

 

 

 

Bhp

 

1200

 

 

665

 

 

0.25

 

 

779

 

0.36

872

 

 

0.48

 

 

957

 

0.60

 

1028

 

 

0.69

 

1300

 

 

699

 

0.30

 

 

809

 

0.42

902

 

 

0.55

 

 

984

 

0.67

 

1058

 

 

0.80

 

1400

 

 

735

 

0.36

 

 

840

 

0.48

933

 

 

0.62

 

 

1011

 

0.75

 

1086

 

 

0.89

 

1500

 

 

770

 

0.42

 

 

873

 

0.55

963

 

 

0.69

 

 

1041

 

0.84

 

1113

 

 

0.99

 

1600

 

 

835

 

0.49

 

 

907

 

0.63

993

 

 

0.77

 

 

1072

 

0.93

 

1141

 

 

1.09

 

1700

 

 

873

 

0.57

 

 

941

 

0.72

1024

 

 

0.87

 

 

1103

 

1.04

 

1171

 

 

1.20

 

1800

 

 

881

 

0.66

 

 

976

 

0.81

1057

 

 

0.97

 

 

1132

 

1.14

 

1202

 

 

1.32

 

1900

 

 

919

 

0.75

 

 

1011

 

0.92

1091

 

 

1.08

 

 

1162

 

1.25

 

1232

 

 

1.45

 

2000

 

 

958

 

0.86

 

 

1046

 

1.03

1125

 

 

1.21

 

 

1195

 

1.38

 

1262

 

 

1.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B048 (4 TONS) — HIGH-STATIC MOTOR (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

 

1.6

 

 

 

1.8

 

 

 

 

2.0

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

 

Bhp

 

Rpm

 

 

Bhp

Rpm

 

Bhp

 

 

 

Rpm

 

Bhp

Rpm

 

 

 

Bhp

 

1200

 

 

1083

 

 

0.74

 

 

1134

 

0.80

1185

 

 

0.88

 

 

1331

 

0.99

 

1374

 

 

1.09

 

1300

 

 

1121

 

0.89

 

 

1171

 

0.94

1219

 

 

1.00

 

 

1268

 

1.10

 

1309

 

 

1.21

 

1400

 

 

1153

 

1.00

 

 

1210

 

1.12

1257

 

 

1.17

 

 

1307

 

1.25

 

1349

 

 

1.37

 

1500

 

 

1180

 

1.13

 

 

1241

 

1.27

1295

 

 

1.37

 

 

1339

 

1.43

 

1382

 

 

1.57

 

1600

 

 

1207

 

1.25

 

 

1269

 

1.40

1326

 

 

1.54

 

 

1376

 

1.65

 

1420

 

 

1.81

 

1700

 

 

1235

 

1.37

 

 

1296

 

1.53

1354

 

 

1.70

 

 

1407

 

1.84

 

1452

 

 

2.02

 

1800

 

 

1263

 

1.49

 

 

1323

 

1.67

1381

 

 

1.85

 

 

1436

 

2.02

 

1482

 

 

2.22

 

1900

 

 

1294

 

1.63

 

 

1351

 

1.81

1408

 

 

2.00

 

 

1463

 

2.19

 

 

 

 

 

2000

 

 

1325

 

1.78

 

 

1362

 

1.97

1436

 

 

2.16

 

 

1489

 

2.36

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 840 to 1185 rpm for standard motor; 1075 to 1455 rpm for high-static motor. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

7.Interpolation is permissible. Do not extrapolate.

27

Page 27
Image 27
Bryant 581B manual PERFORMANCE DATA cont, FAN PERFORMANCE — VERTICAL DISCHARGE UNITS cont