Bryant 581B manual Electrical Data

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 45
Image 45
ELECTRICAL DATA

ELECTRICAL DATA

581B036-072 STANDARD MOTOR (Units Without Electrical Convenience Outlet)

 

NOMINAL

VOLTAGE

 

 

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

COMPRESSOR

OFM

IFM

SUPPLY

DISCONNECT

VOLTAGE

RANGE

FAN MOTOR

581B

 

 

 

 

WITH OUTLET

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

25.6/25.6

35/35

25/25

 

101/101

036

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

18.5/18.5

25/25

18/18

 

90/ 90

(3 Tons)

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

9.0

15

9

 

46

 

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

7.3

15

7

 

36

 

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

35.2/35.2

45/45

34/34

 

142/142

048

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

22.5/22.5

30/30

22/22

 

112/112

(4 Tons)

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

11.9

15

12

 

56

 

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

9.3

15

9

 

45

 

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

46.3/46.3

60/60

45/45

 

216/216

060

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

28.9/28.9

35/35

28/28

 

168/168

(5 Tons)

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

14.7

20

14

 

84

 

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

11.6

15

11

 

67

072

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

32.8/32.8

40/40

32/32

 

200/200

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

15.2

20

15

 

92

(6 Tons)

 

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

12.2

15

13

 

78

 

 

581B036-072 STANDARD MOTOR (Units With Electrical Convenience Outlet)

 

NOMINAL

VOLTAGE

 

 

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

COMPRESSOR

OFM

IFM

SUPPLY

DISCONNECT

RANGE

FAN MOTOR

581B

VOLTAGE

 

 

 

 

WITH OUTLET

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

31.6/31.6

40/40

30/30

 

106/106

036

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

24.5/24.5

30/30

24/24

 

95/95

(3 Tons)

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

11.7

15

11

 

48

 

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

9.5

15

9

 

38

 

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

41.2/41.2

50/50

39/39

 

147/147

048

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

28.5/28.5

35/35

27/27

 

117/117

(4 Tons)

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

14.6

20

14

 

58

 

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

11.5

15

11

 

47

 

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

52.3/52.3

60/60

50/50

 

221/221

060

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

34.9/34.9

40/40

34/34

 

173/173

(5 Tons)

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

17.4

20

17

 

86

 

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

13.8

20

13

 

69

072

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

38.8/38.8

45/45

37/37

 

205/205

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

17.9

20

17

 

94

(6 Tons)

 

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

14.3

20

15

 

79

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Can- ada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.

45