Bryant manual PERFORMANCE DATA cont, 581B120 10 TONS — STANDARD AND HIGH-STATICMOTOR

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 39
Image 39
Manual background

PERFORMANCE DATA (cont)

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

581B120 (10 TONS) — STANDARD AND HIGH-STATIC MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

3000

478

 

0.57

658

 

0.92

721

 

1.08

796

 

1.23

851

 

1.50

898

 

1.78

942

 

2.01

983

 

2.17

1023

 

2.46

1063

 

2.61

3100

500

 

0.62

669

 

0.97

731

 

1.16

808

 

1.30

861

 

1.57

907

 

1.86

951

 

2.09

992

 

2.24

1031

 

2.51

1070

 

2.75

3200

519

 

0.69

680

 

1.03

741

 

1.23

818

 

1.38

873

 

1.65

916

 

1.95

960

 

2.18

1000

 

2.32

1039

 

2.58

1077

 

2.88

3300

537

 

0.77

692

 

1.10

751

 

1.30

828

 

1.47

884

 

1.72

925

 

2.03

969

 

2.27

1009

 

2.41

1048

 

2.66

1086

 

2.95

3400

561

 

0.86

704

 

1.17

761

 

1.37

837

 

1.57

896

 

1.82

934

 

2.12

978

 

2.36

1018

 

2.51

1057

 

2.75

1094

 

3.02

3500

592

 

0.98

715

 

1.24

773

 

1.45

847

 

1.66

907

 

1.92

945

 

2.22

987

 

2.46

1027

 

2.60

1066

 

2.85

1102

 

3.12

3600

632

 

1.12

727

 

1.32

784

 

1.54

857

 

1.76

917

 

2.03

957

 

2.32

996

 

2.55

1036

 

2.71

1075

 

2.96

1111

 

3.22

3700

677

 

1.20

748

 

1.43

810

 

1.65

869

 

1.89

928

 

2.17

984

 

2.43

1036

 

2.68

1080

 

2.90

1114

 

3.07

1135

 

3.17

3800

691

 

1.28

761

 

1.52

822

 

1.75

880

 

1.98

937

 

2.28

993

 

2.55

1046

 

2.81

1092

 

3.05

1129

 

3.25

1156

 

3.39

3900

705

 

1.37

773

 

1.62

834

 

1.86

891

 

2.08

947

 

2.39

1002

 

2.66

1055

 

2.94

1102

 

3.20

1143

 

3.42

1174

 

3.59

4000

720

 

1.47

786

 

1.71

847

 

1.97

902

 

2.19

957

 

2.50

1011

 

2.79

1064

 

3.07

1112

 

3.34

1155

 

3.59

1190

 

3.80

4100

734

 

1.56

800

 

1.82

860

 

2.09

914

 

2.31

967

 

2.60

1021

 

2.91

1072

 

3.20

1121

 

3.49

1165

 

3.76

1203

 

3.99

4200

749

 

1.66

813

 

1.92

873

 

2.21

926

 

2.44

978

 

2.71

1030

 

3.04

1081

 

3.34

1130

 

3.64

1175

 

3.92

1215

 

4.18

4300

764

 

1.77

826

 

2.04

886

 

2.33

938

 

2.57

989

 

2.83

1040

 

3.18

1090

 

3.48

1139

 

3.79

1185

 

4.08

1226

 

4.36

4400

779

 

1.88

840

 

2.16

899

 

2.46

951

 

2.71

1000

 

2.96

1050

 

3.31

1100

 

3.63

1148

 

3.94

1194

 

4.25

1236

 

4.54

4500

793

 

1.99

854

 

2.28

912

 

2.59

963

 

2.86

1012

 

3.09

1061

 

3.43

 

 

 

1157

 

4.09

1203

 

4.42

1246

 

4.72

1109

 

3.78

4600

808

 

2.11

868

 

2.42

925

 

2.73

975

 

3.00

1024

 

3.25

1071

 

3.56

1119

 

3.93

1166

 

4.26

1212

 

4.58

1255

 

4.91

4700

822

 

2.24

882

 

2.56

937

 

2.86

988

 

3.16

1036

 

3.42

1082

 

3.70

1129

 

4.09

1175

 

4.43

1221

 

4.76

1264

 

5.09

4800

837

 

2.37

896

 

2.71

950

 

3.00

1001

 

3.32

1048

 

3.59

1093

 

3.86

1139

 

4.24

1185

 

4.60

1230

 

4.93

 

4900

852

 

2.51

910

 

2.86

963

 

3.15

1014

 

3.48

1060

 

3.76

1105

 

4.02

1150

 

4.38

1194

 

4.77

1239

 

5.12

 

5000

867

 

2.65

924

 

3.01

977

 

3.30

1027

 

3.65

1073

 

3.94

1117

 

4.20

1161

 

4.54

1204

 

4.95

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates high static motor and drive required.

3.Motor drive range is 860 to 1080 rpm for standard motors and 830 to 1130 for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 3.70 for standard motors and 5.25 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

581B150 (121/2 TONS) — STANDARD MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

3700

 

 

 

869

 

1.89

928

 

2.17

984

 

2.43

1036

 

2.68

1080

 

2.90

1114

 

3.07

1135

 

3.17

3800

 

 

 

880

 

1.98

937

 

2.28

993

 

2.55

1046

 

2.81

1092

 

3.05

1129

 

3.25

1156

 

3.39

3900

 

 

 

891

 

2.08

947

 

2.39

1002

 

2.66

1055

 

2.94

1102

 

3.20

1143

 

3.42

1174

 

3.59

4000

 

 

 

902

 

2.19

957

 

2.50

1011

 

2.79

1064

 

3.07

1112

 

3.34

1155

 

3.59

1190

 

3.80

4100

 

 

860

 

2.09

914

 

2.31

967

 

2.60

1021

 

2.91

1072

 

3.20

1121

 

3.49

1165

 

3.76

1203

 

3.99

4200

 

 

873

 

2.21

926

 

2.44

978

 

2.71

1030

 

3.04

1081

 

3.34

1130

 

3.64

1175

 

3.92

1215

 

4.18

4300

 

 

886

 

2.33

938

 

2.57

989

 

2.83

1040

 

3.18

1090

 

3.48

1139

 

3.79

1185

 

4.08

1226

 

4.36

4400

 

 

899

 

2.46

951

 

2.71

1000

 

2.96

1050

 

3.31

1100

 

3.63

1148

 

3.94

1194

 

4.25

1236

 

4.54

4500

 

 

912

 

2.59

963

 

2.86

1012

 

3.09

1061

 

3.43

1109

 

3.78

1157

 

4.09

1203

 

4.42

1246

 

4.72

4600

 

868

 

2.42

925

 

2.73

975

 

3.00

1024

 

3.25

1071

 

3.56

1119

 

3.93

1166

 

4.26

1212

 

4.58

1255

 

4.91

4700

 

882

 

2.56

937

 

2.86

988

 

3.16

1036

 

3.42

1082

 

3.70

1129

 

4.09

1175

 

4.43

1221

 

4.76

1264

 

5.09

4800

 

896

 

2.71

950

 

3.00

1001

 

3.32

1048

 

3.59

1093

 

3.86

1139

 

4.24

1185

 

4.60

1230

 

4.93

 

4900

 

910

 

2.86

963

 

3.15

1014

 

3.48

1060

 

3.76

1105

 

4.02

1150

 

4.38

1194

 

4.77

1239

 

5.12

 

5000

867

 

2.65

924

 

3.01

977

 

3.30

1027

 

3.65

1073

 

3.94

1117

 

4.20

1161

 

4.54

1204

 

4.95

 

 

5100

882

 

2.79

938

 

3.17

990

 

3.46

1040

 

3.82

1085

 

4.12

1129

 

4.40

1172

 

4.71

1214

 

5.13

 

 

5200

896

 

2.95

952

 

3.33

1003

 

3.63

1053

 

4.00

1098

 

4.30

1141

 

4.60

1183

 

4.91

 

 

 

5300

911

 

3.11

967

 

3.50

1017

 

3.80

1066

 

4.18

1111

 

4.50

1153

 

4.80

1194

 

5.08

 

 

 

5400

926

 

3.27

981

 

3.68

1030

 

3.98

1079

 

4.35

1124

 

4.70

1166

 

5.01

 

 

 

 

5500

940

 

3.44

995

 

3.86

1044

 

4.17

1092

 

4.54

1137

 

4.91

1178

 

5.22

 

 

 

 

5600

955

 

3.62

1010

 

4.04

1058

 

4.38

1105

 

4.73

1150

 

5.12

 

 

 

 

 

5700

970

 

3.80

1024

 

4.23

1072

 

4.59

1118

 

4.93

 

 

 

 

 

 

5800

985

 

3.99

1039

 

4.42

1086

 

4.80

1131

 

5.14

 

 

 

 

 

 

5900

1000

 

4.18

1053

 

4.62

1100

 

5.02

 

 

 

 

 

6000

1015

 

4.39

1068

 

4.83

1114

 

5.25

 

 

 

 

 

6100

1030

 

4.59

1083

 

5.04

 

 

 

 

 

 

6200

1046

 

4.81

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 2.)

2.Standard drive range is 900 to 1260 rpm.

3.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 5.25 for the standard motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data table on pages 41 and 42 for addi- tional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

6.Interpolation is permissible. Do not extrapolate.

39

Page 39
Image 39
Bryant manual PERFORMANCE DATA cont, 581B120 10 TONS — STANDARD AND HIGH-STATICMOTOR