581B120 (10 TONS) — STANDARD AND HIGH-STATIC MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

3000

556

 

0.65

624

 

0.81

682

0.95

737

0.99

745

1.04

750

 

1.12

809

 

1.24

875

 

1.40

899

 

1.56

950

 

1.92

3100

569

 

0.70

636

 

0.87

693

1.01

748

1.08

755

1.12

757

 

1.20

862

 

1.38

903

 

1.53

943

 

1.88

971

 

2.21

3200

583

 

0.76

649

 

0.94

705

1.08

758

1.17

787

1.30

769

 

1.36

905

 

1.52

971

 

1.86

982

 

2.19

992

 

2.41

3300

597

 

0.83

662

 

1.00

717

1.16

770

1.29

815

1.37

780

 

1.43

965

 

1.82

991

 

2.10

1000

 

2.40

1025

 

2.59

3400

611

 

0.90

675

 

1.08

730

1.23

781

1.41

830

1.50

838

 

1.63

992

 

2.11

1015

 

2.43

1030

 

2.62

1050

 

2.72

3500

625

 

0.97

688

 

1.15

742

1.32

792

1.49

840

1.64

860

 

1.85

1011

 

2.45

1028

 

2.62

1072

 

2.74

1099

 

2.90

3600

639

 

1.04

701

 

1.23

755

1.41

803

1.57

850

1.87

890

 

2.21

1026

 

2.55

1063

 

2.75

1095

 

2.89

1119

 

3.08

3700

729

 

1.36

790

 

1.58

847

1.79

902

2.06

955

2.29

1008

 

2.55

1060

 

2.80

1108

 

3.05

1152

 

3.27

1190

 

3.46

3800

745

 

1.46

805

 

1.69

861

1.89

915

2.17

967

2.41

1019

 

2.67

1070

 

2.94

1118

 

3.19

1163

 

3.44

1203

 

3.65

3900

761

 

1.56

820

 

1.80

875

2.01

928

2.29

979

2.55

1029

 

2.80

1079

 

3.07

1128

 

3.34

1173

 

3.60

1214

 

3.83

4000

777

 

1.67

836

 

1.92

889

2.14

941

2.40

991

2.68

1040

 

2.94

1089

 

3.22

1137

 

3.49

1183

 

3.76

1225

 

4.00

4100

793

 

1.79

851

 

2.05

904

2.27

955

2.52

1004

2.82

1052

 

3.08

1100

 

3.36

1147

 

3.65

1193

 

3.93

1236

 

4.19

4200

810

 

1.91

867

 

2.18

918

2.41

968

2.65

1017

2.96

1064

 

3.23

1110

 

3.51

1157

 

3.81

1202

 

4.09

1245

 

4.38

4300

826

 

2.04

883

 

2.32

933

2.55

982

2.79

1030

3.11

1076

 

3.40

1121

 

3.67

1167

 

3.97

1212

 

4.27

1255

 

4.56

4400

842

 

2.17

898

 

2.46

948

2.70

996

2.93

1043

3.25

1088

 

3.56

1133

 

3.84

1178

 

4.14

1222

 

4.44

1265

 

4.74

4500

859

 

2.31

914

 

2.60

962

2.85

1010

3.09

1056

3.40

 

 

 

1144

 

4.00

1188

 

4.31

1232

 

4.62

1274

 

4.93

1101

 

3.73

4600

876

 

2.45

930

 

2.76

977

3.01

1024

3.26

1070

3.55

1114

 

3.90

1157

 

4.19

1199

 

4.49

1242

 

4.81

1284

 

5.13

4700

892

 

2.60

945

 

2.91

992

3.18

1039

3.43

1083

3.71

1126

 

4.07

1169

 

4.38

1210

 

4.68

1252

 

5.00

 

4800

909

 

2.77

961

 

3.07

1008

3.36

1053

3.61

1097

3.88

1140

 

4.25

1181

 

4.58

1222

 

4.87

1263

 

5.20

 

4900

926

 

2.93

977

 

3.24

1024

3.54

1068

3.80

1111

4.06

1153

 

4.41

1194

 

4.77

1234

 

5.09

 

 

5000

942

 

3.11

993

 

3.41

1039

3.73

1080

3.99

1125

4.25

1166

 

4.59

1207

 

4.97

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates high static motor and drive required.

3.Motor drive range is 860 to 1080 rpm for standard motors; 830 to 1130 rpm for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 3.70 for standard motors, 5.25 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or prema- ture motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

581B150 (121/2 TONS) — STANDARD MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

3700

 

 

 

902

 

2.06

955

 

2.29

1008

 

2.55

1060

 

2.80

1108

 

3.05

1152

 

3.27

1190

 

3.46

3800

 

 

861

 

1.89

915

 

2.17

967

 

2.41

1019

 

2.67

1070

 

2.94

1118

 

3.19

1163

 

3.44

1203

 

3.65

3900

 

 

875

 

2.01

928

 

2.29

979

 

2.55

1029

 

2.80

1079

 

3.07

1128

 

3.34

1173

 

3.60

1214

 

3.83

4000

 

 

889

 

2.14

941

 

2.40

991

 

2.68

1040

 

2.94

1089

 

3.22

1137

 

3.49

1183

 

3.76

1225

 

4.00

4100

 

 

904

 

2.27

955

 

2.52

1004

 

2.82

1052

 

3.08

1100

 

3.36

1147

 

3.65

1193

 

3.93

1236

 

4.19

4200

 

867

 

2.18

918

 

2.41

968

 

2.65

1017

 

2.96

1064

 

3.23

1110

 

3.51

1157

 

3.81

1202

 

4.09

1245

 

4.38

4300

 

883

 

2.32

933

 

2.55

982

 

2.79

1030

 

3.11

1076

 

3.40

1121

 

3.67

1167

 

3.97

1212

 

4.27

1255

 

4.56

4400

 

898

 

2.46

948

 

2.70

996

 

2.93

1043

 

3.25

1088

 

3.56

1133

 

3.84

1178

 

4.14

1222

 

4.44

1265

 

4.74

4500

 

914

 

2.60

962

 

2.85

1010

 

3.09

1056

 

3.40

1101

 

3.73

1144

 

4.00

1188

 

4.31

1232

 

4.62

1274

 

4.93

4600

876

 

2.45

930

 

2.76

977

 

3.01

1024

 

3.26

1070

 

3.55

1114

 

3.90

1157

 

4.19

1199

 

4.49

1242

 

4.81

1284

 

5.13

4700

892

 

2.60

945

 

2.91

992

 

3.18

1039

 

3.43

1083

 

3.71

1126

 

4.07

1169

 

4.38

1210

 

4.68

1252

 

5.00

 

4800

909

 

2.77

961

 

3.07

1008

 

3.36

1053

 

3.61

1097

 

3.88

1140

 

4.25

1181

 

4.58

1222

 

4.87

1263

 

5.20

 

4900

926

 

2.93

977

 

3.24

1024

 

3.54

1068

 

3.80

1111

 

4.06

1153

 

4.41

1194

 

4.77

1234

 

5.09

 

 

5000

942

 

3.11

993

 

3.41

1039

 

3.73

1080

 

3.99

1125

 

4.25

1166

 

4.59

1207

 

4.97

 

 

 

5100

959

 

3.29

1009

 

3.60

1055

 

3.92

1097

 

4.19

1139

 

4.46

1180

 

4.78

1220

 

5.18

 

 

 

5200

976

 

3.47

1025

 

3.78

1071

 

4.12

1112

 

4.40

1153

 

4.67

1194

 

4.98

 

 

 

 

5300

993

 

3.67

1041

 

3.98

1086

 

4.33

1127

 

4.61

1168

 

4.90

1208

 

5.19

 

 

 

 

5400

1010

 

3.87

1057

 

4.18

1102

 

4.54

1142

 

4.84

1182

 

5.13

 

 

 

 

 

5500

1027

 

4.07

1073

 

4.39

1118

 

4.76

1157

 

5.07

 

 

 

 

 

 

5600

1043

 

4.29

1090

 

4.61

1133

 

4.99

 

 

 

 

 

5700

1060

 

4.51

1106

 

4.83

1149

 

5.22

 

 

 

 

 

5800

1077

 

4.74

1122

 

5.07

 

 

 

 

 

 

5900

1094

 

4.98

 

 

 

 

 

 

 

6000

1111

 

5.22

 

 

 

 

 

 

 

6100

 

 

 

 

 

 

 

 

6200

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 2.)

2.Standard drive range is 900 to 1260 rpm.

3.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 5.25 for standard motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data table on pages 41 and 42 for additional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

6.Interpolation is permissible. Do not extrapolate.

32

Page 32
Image 32
Bryant manual PERFORMANCE DATA cont, 581B120 10 TONS - STANDARD AND HIGH-STATICMOTOR