EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS

PERFORMANCE DATA (cont)

EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS

UNIT

UNIT

MAXIMUM

MAXIMUM

UNIT VOLTAGE

MAXIMUM

581B

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

 

 

 

 

 

208/230

6.7

036

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

 

 

 

 

208/230

6.7

046

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

 

 

 

 

208/230

8.6

060

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

 

 

 

 

208/230

8.6

072

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

 

 

 

 

208/230

12.2

090,102

Three

4.20

3775

460

5.5

 

 

 

 

575

5.5

 

 

 

 

208/230

17.5

120

Three

5.25

4400

460

8.5

 

 

 

 

575

8.5

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.