PERFORMANCE DATA (cont)
EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS
UNIT | UNIT | MAXIMUM | MAXIMUM | UNIT VOLTAGE | MAXIMUM | |
581B | PHASE | CONTINUOUS BHP* | OPERATING WATTS* | AMP DRAW | ||
| ||||||
|
|
|
| 208/230 | 6.7 | |
036 | Three | 2.40 | 2120 | 460 | 3.0 | |
|
|
|
| 575 | 3.0 | |
|
|
|
| 208/230 | 6.7 | |
046 | Three | 2.40 | 2120 | 460 | 3.0 | |
|
|
|
| 575 | 3.0 | |
|
|
|
| 208/230 | 8.6 | |
060 | Three | 2.90 | 2615 | 460 | 3.9 | |
|
|
|
| 575 | 3.9 | |
|
|
|
| 208/230 | 8.6 | |
072 | Three | 2.90 | 2615 | 460 | 3.9 | |
|
|
|
| 575 | 3.9 | |
|
|
|
| 208/230 | 12.2 | |
090,102 | Three | 4.20 | 3775 | 460 | 5.5 | |
|
|
|
| 575 | 5.5 | |
|
|
|
| 208/230 | 17.5 | |
120 | Three | 5.25 | 4400 | 460 | 8.5 | |
|
|
|
| 575 | 8.5 |
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Durablade Economizer Barometric Relief Damper Characteristics —
Durablade Economizer Barometric Relief Damper Characteristics —
42