Bryant manual PERFORMANCE DATA cont, 581B102 81/2 TONS — STANDARD MOTOR

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 38
Image 38
Manual background

PERFORMANCE DATA (cont)

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

581B102 (81/2 TONS) — STANDARD MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

0.9

 

1.0

 

1.2

 

1.4

 

1.6

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

2550

550

 

0.69

627

 

0.94

692

 

1.17

754

 

1.45

783

 

1.60

812

 

1.74

864

 

1.99

920

 

2.39

974

 

2.76

2600

557

 

0.72

634

 

0.97

698

 

1.21

759

 

1.49

787

 

1.64

816

 

1.79

868

 

2.04

921

 

2.41

976

 

2.78

2700

573

 

0.79

648

 

1.05

711

 

1.29

770

 

1.58

798

 

1.73

827

 

1.88

878

 

2.16

928

 

2.45

983

 

2.88

2800

588

 

0.86

662

 

1.13

723

 

1.38

782

 

1.66

809

 

1.82

837

 

1.98

889

 

2.29

937

 

2.57

986

 

2.91

2900

604

 

0.94

676

 

1.21

737

 

1.48

794

 

1.76

821

 

1.92

848

 

2.08

900

 

2.41

947

 

2.70

993

 

3.01

3000

620

 

1.02

690

 

1.30

750

 

1.58

806

 

1.86

832

 

2.02

849

 

2.18

910

 

2.52

958

 

2.85

1002

 

3.15

3100

636

 

1.11

704

 

1.39

764

 

1.69

818

 

1.97

844

 

2.13

870

 

2.29

920

 

2.64

968

 

2.99

1012

 

3.30

3200

652

 

1.21

718

 

1.49

778

 

1.80

831

 

2.09

856

 

2.25

882

 

2.40

931

 

2.76

979

 

3.13

1023

 

3.47

3300

668

 

1.31

732

 

1.59

793

 

1.92

844

 

2.21

869

 

2.37

894

 

2.53

942

 

2.89

989

 

3.26

1034

 

3.63

3400

684

 

1.41

747

 

1.70

807

 

2.04

857

 

2.35

882

 

2.51

907

 

2.66

954

 

3.02

1000

 

3.40

1044

 

3.79

3500

701

 

1.53

762

 

1.82

821

 

2.16

871

 

2.48

895

 

2.64

919

 

2.80

966

 

3.15

1011

 

3.55

1054

 

3.94

3600

717

 

1.65

777

 

1.94

835

 

2.29

885

 

2.63

908

 

2.79

932

 

2.95

978

 

3.30

1022

 

3.69

1065

 

4.10

3700

733

 

1.77

792

 

2.07

849

 

2.42

899

 

2.78

922

 

2.95

945

 

3.11

990

 

3.45

1034

 

3.84

1076

 

4.26

3750

742

 

1.84

800

 

2.14

856

 

2.49

907

 

2.86

929

 

3.03

952

 

3.20

997

 

3.54

1040

 

3.93

1082

 

4.27

3800

750

 

1.90

807

 

2.21

863

 

2.56

914

 

2.93

936

 

3.11

958

 

3.28

1003

 

3.62

1045

 

4.01

1087

 

4.43

3900

767

 

2.04

822

 

2.35

877

 

2.71

928

 

3.09

950

 

3.27

972

 

3.45

1015

 

3.80

1057

 

4.18

1098

 

4.60

4000

783

 

2.18

838

 

2.50

891

 

2.86

942

 

3.26

964

 

3.45

986

 

3.63

1028

 

3.99

1070

 

4.36

1110

 

4.78

4100

800

 

2.34

854

 

2.66

905

 

3.02

956

 

3.43

978

 

3.62

1000

 

3.81

1042

 

4.18

1082

 

4.56

1122

 

4.97

4200

817

 

2.49

869

 

2.82

920

 

3.19

970

 

3.60

992

 

3.80

1015

 

4.00

1055

 

4.38

1095

 

4.76

1134

 

5.16

4250

826

 

2.58

877

 

2.91

928

 

3.28

977

 

3.69

999

 

3.90

1022

 

4.10

1062

 

4.49

1102

 

4.87

 

4300

834

 

2.66

885

 

3.00

935

 

3.37

984

 

3.78

1006

 

3.99

1029

 

4.20

1069

 

4.59

1108

 

4.98

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 840 to 1085 rpm for standard motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 2.9 for standard motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for addi- tional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

581B102 (81/2 TONS) — HIGH-STATIC MOTOR

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

2550

550

 

0.69

627

 

0.94

692

 

1.17

754

 

1.45

812

 

1.74

864

 

1.99

920

 

2.39

974

 

2.76

1005

 

3.04

1034

 

3.31

2600

557

 

0.72

634

 

0.97

698

 

1.21

759

 

1.49

816

 

1.79

868

 

2.04

921

 

2.41

976

 

2.78

1008

 

3.06

1037

 

3.33

2700

573

 

0.79

648

 

1.05

711

 

1.29

770

 

1.58

827

 

1.88

878

 

2.16

928

 

2.45

983

 

2.88

1015

 

3.17

1044

 

3.45

2800

588

 

0.86

662

 

1.13

723

 

1.38

782

 

1.66

837

 

1.98

889

 

2.29

937

 

2.57

986

 

2.91

1018

 

3.20

1047

 

3.49

2900

604

 

0.94

676

 

1.21

737

 

1.48

794

 

1.76

848

 

2.08

900

 

2.41

947

 

2.70

993

 

3.01

1025

 

3.31

1055

 

3.61

3000

620

 

1.02

690

 

1.30

750

 

1.58

806

 

1.86

849

 

2.18

910

 

2.52

958

 

2.85

1002

 

3.15

1034

 

3.47

1064

 

3.77

3100

636

 

1.11

704

 

1.39

764

 

1.69

818

 

1.97

870

 

2.29

920

 

2.64

968

 

2.99

1012

 

3.30

1045

 

3.63

1075

 

3.95

3200

652

 

1.21

718

 

1.49

778

 

1.80

831

 

2.09

882

 

2.40

931

 

2.76

979

 

3.13

1023

 

3.47

1056

 

3.82

1087

 

4.16

3300

668

 

1.31

732

 

1.59

793

 

1.92

844

 

2.21

894

 

2.53

942

 

2.89

989

 

3.26

1034

 

3.63

1067

 

3.99

 

 

 

 

 

 

 

 

1098

 

4.35

3400

684

 

1.41

747

 

1.70

807

 

2.04

857

 

2.35

907

 

2.66

954

 

3.02

1000

 

3.40

1044

 

3.79

1078

 

4.17

1109

 

4.54

3500

701

 

1.53

762

 

1.82

821

 

2.16

871

 

2.48

919

 

2.80

966

 

3.15

1011

 

3.55

1054

 

3.94

1088

 

4.33

1119

 

4.72

3600

717

 

1.65

777

 

1.94

835

 

2.29

885

 

2.63

932

 

2.95

978

 

3.30

1022

 

3.69

1065

 

4.10

1099

 

4.51

1131

 

4.91

3700

733

 

1.77

792

 

2.07

849

 

2.42

899

 

2.78

945

 

3.11

990

 

3.45

1034

 

3.84

1076

 

4.26

1111

 

4.69

1143

 

5.10

3750

742

 

1.84

800

 

2.14

856

 

2.49

907

 

2.86

952

 

3.20

997

 

3.54

1040

 

3.93

1082

 

4.27

1117

 

4.70

1149

 

5.12

3800

750

 

1.90

807

 

2.21

863

 

2.56

914

 

2.93

958

 

3.28

1003

 

3.62

1045

 

4.01

1087

 

4.43

1122

 

4.87

1155

 

5.31

3900

767

 

2.04

822

 

2.35

877

 

2.71

928

 

3.09

972

 

3.45

1015

 

3.80

1057

 

4.18

1098

 

4.60

1133

 

5.06

1166

 

5.51

4000

783

 

2.18

838

 

2.50

891

 

2.86

942

 

3.26

986

 

3.63

1028

 

3.99

1070

 

4.36

1110

 

4.78

1146

 

5.26

1179

 

5.73

4100

800

 

2.34

854

 

2.66

905

 

3.02

956

 

3.43

1000

 

3.81

1042

 

4.18

1082

 

4.56

1122

 

4.97

1158

 

5.47

1192

 

5.95

4200

817

 

2.49

869

 

2.82

920

 

3.19

970

 

3.60

1015

 

4.00

1055

 

4.38

1095

 

4.76

1134

 

5.16

1171

 

5.68

1204

 

6.18

4250

826

 

2.58

877

 

2.91

928

 

3.28

977

 

3.69

1022

 

4.10

1062

 

4.49

1102

 

4.87

1140

 

5.27

1177

 

5.80

1211

 

6.31

4300

834

 

2.66

885

 

3.00

935

 

3.37

984

 

3.78

 

 

 

1069

 

4.59

1108

 

4.98

1147

 

5.38

1184

 

5.92

1218

 

6.45

1029

 

4.20

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 860 to 1080 rpm for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 40 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 4.2 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for addi- tional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.

7.Interpolation is permissible. Do not extrapolate.

38

Page 38
Image 38