Image 6
OPTIONS AND ACCESSORIES

OPTIONS AND ACCESSORIES

ITEM

OPTION*

ACCESSORY†

Perfect Humidity™ Dehumidification Package

X

 

Integrated Economizer — Durablade

X

X

Integrated Economizer — EconoMi$er (gear driven)

X

X

EconoMi$er with Power Exhaust (Vertical Only)

 

X

Power Exhaust for EconoMi$er

 

X

High-Static Motor (except 150)

X

 

Hinged Access Panels

X

 

25% Manual Outdoor-Air Damper

X

X

50% Manual Outdoor-Air Damper

 

X

Convenience Outlet

X

 

Unit Mounted Disconnect

X

 

Two-Position Damper (25% Open)

 

X

Two-Position Damper (100% Open)

 

X

Roof Curb (14 in.)

 

X

Roof Curb (24 in.)

 

X

Thru-the-Bottom Service Connections

 

X

Thermostat and Subbase

 

X

Light Commercial Thermostat

 

X

Light Commercial Thermidistat

 

X

Time Guard® II Control Circuit (3-Phase Units Only)

 

X

Motormaster® Low Ambient Control

 

X

Motormaster II Low Ambient Control

 

X

Motormaster IV Low Ambient Control

 

X

Accusensor™ II Enthalpy Control

 

X

Accusensor III Differential Enthalpy Sensor

 

X

Liquid Propane Conversion Kit

 

X

Flue Discharge Deflector

 

X

Flue-Hood Protector Assembly

 

X

Coil Guard Grille

 

X

Condenser Coil Hail Guard

 

X

Fan/Filter Status Switch

 

X

Corrosion Resistant Coils

X

 

*Indicates a factory-installed option.

 

 

†Indicates a field-installed accessory.

 

 

LOW AMBIENT CONTROLS

The 581B036-150 standard units are designed to operate in cooling at outdoor temperatures down to 25 F. With accessory Motormaster control (condenser-fan speed modulation), or Motor- master II control (condenser-fan cycling), units can operate at outdoor temperatures down to

–20 F. The head pressure controls, which mount in the condenser section, control the condenser-fan motor to maintain correct condensing temperature.

MOTORMASTER I

MOTORMASTER II

TIME GUARD II CONTROL

Time Guard II Control automatically prevents compressor from restarting for at least 5 minutes after a shutdown. Field-installed accessory prevents short cycling of com- pressor if thermostat is rapidly changed. Time Guard II device mounts in the control compartment of unit. The Time Guard II device is not required when a programma- ble thermostat is applied.

LIQUID PROPANE CONVERSION KIT

BURNER SPUDS (ORIFICES)

Liquid propane conversion kit allows the unit to utilize a liquid propane fuel supply in areas where natural gas is not available. (Kit shown is for sizes 036-072.)

6