Bryant manual PERFORMANCE DATA cont, 581B090 71/2 TONS

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 20
Image 20

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

 

 

 

581B090 (71/2 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

Air Ent

 

2250/0.10

 

 

 

 

 

 

 

3000/0.11

 

 

 

 

 

3750/0.14

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb

 

 

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

 

72

 

67

 

62

 

72

 

 

67

 

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

105.5

 

96.9

 

87.6

 

107.3

 

99.6

 

90.7

 

110.3

 

101.9

 

93.8

 

 

 

 

 

 

 

SHC

 

50.6

 

63.6

 

75.7

 

 

53.3

 

69.2

 

83.7

 

58.0

 

76.6

 

92.2

 

 

 

 

 

 

 

 

 

kW

 

5.15

 

5.07

 

5.04

 

 

5.16

 

5.11

 

5.06

 

5.20

 

5.13

 

5.07

 

 

 

 

 

 

 

 

 

TC

 

102.5

 

93.6

 

83.6

 

105.1

 

96.5

 

87.5

 

107.7

 

99.0

 

90.6

 

 

 

 

 

 

85

 

SHC

 

49.7

 

62.4

 

73.9

 

 

52.8

 

68.4

 

82.2

 

57.3

 

75.9

 

90.0

 

 

 

 

 

 

 

 

 

kW

 

5.86

 

5.79

 

5.73

 

 

5.89

 

5.82

 

5.77

 

5.93

 

5.86

 

5.78

 

 

 

 

 

 

95

 

TC

 

98.9

 

90.1

 

79.3

 

101.6

 

92.9

 

83.5

 

103.8

 

95.3

 

87.4

 

 

 

 

 

 

 

SHC

 

48.5

 

61.2

 

71.9

 

 

51.9

 

67.2

 

80.2

 

56.2

 

74.9

 

87.3

 

 

 

 

 

 

 

 

 

kW

 

6.65

 

6.58

 

6.49

 

 

6.69

 

6.61

 

6.53

 

6.72

 

6.64

 

6.57

 

 

 

 

 

 

 

 

 

TC

 

95.3

 

86.2

 

75.7

 

 

97.6

 

88.8

 

79.6

 

100.0

 

91.0

 

84.1

 

 

 

 

 

 

105

 

SHC

 

47.3

 

59.6

 

70.2

 

 

50.7

 

65.9

 

78.0

 

55.3

 

73.6

 

84.1

 

 

 

 

 

 

 

 

 

kW

 

7.51

 

7.44

 

7.31

 

 

7.55

 

7.48

 

7.36

 

7.59

 

7.50

 

7.41

 

 

 

 

 

 

 

 

 

TC

 

91.0

 

82.0

 

71.6

 

 

93.2

 

84.5

 

75.4

 

95.6

 

86.6

 

80.7

 

 

 

 

 

 

115

 

SHC

 

45.9

 

58.0

 

68.1

 

 

49.3

 

64.2

 

75.3

 

54.2

 

72.1

 

80.7

 

 

 

 

 

 

 

 

 

kW

 

8.43

 

8.33

 

8.20

 

 

8.46

 

8.37

 

8.27

 

8.52

 

8.42

 

8.34

 

 

 

 

 

 

 

 

 

TC

 

86.2

 

77.8

 

68.1

 

 

88.3

 

80.0

 

71.9

 

90.0

 

81.9

 

77.2

 

 

 

 

 

 

125

 

SHC

 

44.1

 

56.4

 

66.3

 

 

47.5

 

62.6

 

71.8

 

52.1

 

70.1

 

77.2

 

 

 

 

 

 

 

 

 

kW

 

9.38

 

9.29

 

9.14

 

 

9.43

 

9.34

 

9.24

 

9.47

 

9.38

 

9.32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B102 (81/2 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F) Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

 

Air Ent

 

 

 

2550/0.08

 

 

 

 

 

3000/0.09

 

 

 

 

3400/0.11

 

 

 

 

 

 

4250/0.13

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F) Air Entering Evaporator — Ewb

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

 

67

 

 

62

 

 

72

 

 

67

 

 

62

 

72

 

67

 

62

 

72

67

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

119.5

 

105.7

 

94.8

 

123.1

 

109.1

 

 

98.7

 

124.8

 

110.7

 

100.2

 

126.3

112.8

103.4

75

 

SHC

 

56.5

 

65.7

 

77.8

 

60.2

 

 

71.7

 

 

86.3

 

62.2

 

75.8

 

92.8

 

67.8

83.3

101.2

 

 

kW

 

5.92

 

 

5.84

 

5.77

 

5.95

 

 

5.88

 

 

5.81

 

5.96

 

5.89

 

5.83

 

5.99

5.91

5.85

 

 

TC

 

115.5

 

101.9

 

90.6

 

119.7

 

105.4

 

 

94.8

 

121.4

 

106.9

 

96.1

 

124.0

109.1

98.7

85

 

SHC

 

55.1

 

64.3

 

76.1

 

58.9

 

 

70.5

 

 

85.1

 

61.3

 

74.5

 

90.5

 

66.2

82.9

98.5

 

 

kW

 

6.77

 

 

6.69

 

6.61

 

6.83

 

 

6.74

 

 

6.67

 

6.85

 

6.76

 

6.67

 

6.88

6.79

6.71

95

 

TC

 

111.3

 

97.7

 

86.6

 

115.0

 

101.2

 

 

90.6

 

117.2

 

102.6

 

91.7

 

120.1

104.8

94.5

 

SHC

 

53.7

 

62.8

 

74.2

 

57.4

 

 

68.9

 

 

82.9

 

60.0

 

73.0

 

88.6

 

65.0

81.5

94.5

 

 

kW

 

7.71

 

 

7.62

 

7.52

 

7.76

 

 

7.68

 

 

7.59

 

7.80

 

7.69

 

7.58

 

7.84

7.74

7.66

 

 

TC

 

107.2

 

93.5

 

82.5

 

110.5

 

 

96.7

 

 

85.9

 

112.1

 

97.9

 

87.6

 

114.9

99.9

90.5

105

 

SHC

 

52.2

 

61.3

 

72.7

 

56.0

 

 

67.4

 

 

81.2

 

58.4

 

71.4

 

86.6

 

63.5

79.5

90.5

 

 

kW

 

8.75

 

 

8.64

 

8.54

 

8.80

 

 

8.70

 

 

8.61

 

8.82

 

8.71

 

8.62

 

8.86

8.75

8.67

 

 

TC

 

101.9

 

89.2

 

78.0

 

104.7

 

 

91.8

 

 

81.5

 

106.7

 

93.1

 

83.3

 

109.2

94.9

86.3

115

 

SHC

 

50.2

 

59.5

 

70.7

 

53.7

 

 

65.7

 

 

79.5

 

56.6

 

69.5

 

83.1

 

61.5

77.8

86.3

 

 

kW

 

9.80

 

 

9.73

 

9.64

 

9.86

 

 

9.79

 

 

9.72

 

9.90

 

9.79

 

9.71

 

9.95

9.84

9.75

 

 

TC

 

97.3

 

 

84.3

 

73.1

 

100.0

 

 

86.8

 

 

76.0

 

101.3

 

87.9

 

78.7

 

102.9

89.5

81.9

125

 

SHC

 

48.7

 

 

57.7

 

68.5

 

52.4

 

 

63.9

 

 

76.0

 

54.8

 

67.9

 

78.7

 

59.1

75.7

81.9

 

 

kW

 

11.03

 

10.90

 

10.70

 

11.08

 

10.96

 

10.81

 

11.11

 

10.99

 

10.88

 

11.14

11.03

10.93

581B090 (71/2 TONS) Standard Ratings

LEGEND

BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb

kW — Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb = tedb

sensible heat capacity (Btuh)

1.10 x cfm

 

tlwb = wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

 

4.5 x cfm

Where hewb = Enthalpy of air entering indoor coil.

3.The SHC is based on 80 F edb temperature of air entering evap- orator coil.

Below 80 F db, subtract (corr factor x cfm) from SHC. Above 80 F db, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (db – 80).

20

Page 20
Image 20
Bryant manual PERFORMANCE DATA cont, 581B090 71/2 TONS