Bryant 581B manual ELECTRICAL DATA cont

Models: 581B

1 64
Download 64 pages 44.36 Kb
Page 46
Image 46
ELECTRICAL DATA (cont)

ELECTRICAL DATA (cont)

581B036-072 HIGH-STATIC MOTOR (Units Without Electrical Convenience Outlet)

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

 

(each)

FAN MOTOR

SUPPLY

581B

 

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

 

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

 

208/230-3-60

187

254

10.3

 

77.0

0.7

5.8

0.6

19.4/19.4

25/25

19/19

 

120/120

036

460-3-60

414

508

5.1

 

39.0

0.4

2.6

0.3

9.4

15

9

 

60

 

575-3-60

518

632

4.2

 

31.0

0.4

2.6

0.3

7.7

15

8

 

48

 

208/230-3-60

187

254

13.5

 

99.0

0.7

5.8

0.6

23.4/23.4

30/30

23/23

 

142/142

048

460-3-60

414

508

7.4

 

49.5

0.4

2.6

0.3

12.3

15

12

 

71

 

575-3-60

518

632

5.8

 

40.0

0.4

2.6

0.3

9.7

15

9

 

57

 

208/230-3-60

187

254

17.3

 

123.0

1.5

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

060

460-3-60

414

508

9.0

 

62.0

0.8

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.1

 

50.0

0.8

3.4

0.3

12.2

15

12

 

76

 

208/230-3-60

187

254

20.5

 

156.0

1.4

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

072

460-3-60

414

508

9.6

 

70.0

0.6

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.7

 

56.0

0.6

3.4

0.3

12.2

15

12

 

76

581B036-072 HIGH-STATIC MOTOR (Units With Electrical Convenience Outlet)

 

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

 

(each)

FAN MOTOR

SUPPLY

581B

 

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

 

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

 

 

 

 

 

 

208/230-3-60

187

254

10.3

 

77.0

0.7

5.8

0.6

25.4/25.4

30/30

25

124/124

036

 

460-3-60

414

508

5.1

 

39.0

0.4

2.6

0.3

12.1

15

12

63

 

 

575-3-60

518

632

4.2

 

31.0

0.4

2.6

0.3

9.8

15

10

50

 

 

208/230-3-60

187

254

13.5

 

99.0

0.7

5.8

0.6

29.4/29.4

35/35

29

146/146

048

 

460-3-60

414

508

7.4

 

49.5

0.4

2.6

0.3

15.0

20

14

73

 

 

575-3-60

518

632

5.8

 

40.0

0.4

2.6

0.3

11.8

15

11

59

 

 

208/230-3-60

187

254

17.3

 

123.0

1.5

7.5

0.6

36.6/36.6

40/40

36

192/192

060

 

460-3-60

414

508

9.0

 

62.0

0.8

3.4

0.3

18.2

20

18

96

 

 

575-3-60

518

632

7.1

 

50.0

0.8

3.4

0.3

14.4

20

14

77

 

 

208/230-3-60

187

254

20.5

 

156.0

1.4

7.5

0.6

40.5/40.5

45/45

39

224/224

072

 

460-3-60

414

508

9.6

 

70.0

0.6

3.4

0.3

18.7

25

18

104

 

 

575-3-60

518

632

7.7

 

56.0

0.6

3.4

0.3

15.0

20

15

89

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the overcur- rent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

 

7

457

 

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

46

Page 46
Image 46
Bryant 581B manual ELECTRICAL DATA cont