If the supply-air temperature falls below 52 F, a switch on the supply-air thermostat is closed between the T1 terminal and the 24 vac terminal. This causes the damper to modulate closed until the supply-air temperature rises above 55 F or the damper reaches the minimum position.
When the supply-air temperature is between 55 F and 57 F, the supply-air thermostat has open switches between the T2 and 24 vac terminals. This causes the economizer damper to remain in an intermediate open position.
If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second stage cooling. Compres- sor no. 1 and condenser fan will be energized, and the position of the economizer damper will be determined by the supply-air temperature. Compressor no. 2 is locked out.
When the second stage of cooling is satisfied, the compressor and condenser fan motors will be deenergized. The damper position will be determined by the supply-air temperature.
When the first stage of cooling is satisfied, the IFM shuts off after a 30-second delay. The damper then moves to fully closed position.
Cooling, Units With EconoMi$er — When the outdoor-air temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G +Y1), the indoor-fan motor (IFM) is energized and the EconoMi$er damper modulates to minimum position. The compressor con- tactor is energized starting the compressor and outdoor-fan motor (OFM). After the thermostat is satisfied, the damper mod- ulates to the fully closed position when the IFM is deenergized.
When the OAT is below the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor air dampers to maintain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor-air damper modules closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position.
Heating, Units Without Economizer — When the thermostat calls for heating, terminal W1 is energized. In order to prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced- draft motor (IDM) is then energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. When additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 and W2 are deenergized, the IFM stops after a 45-secondtime-off delay.
Heating, Units With Economizer or Two-Position Damper — When the thermostat calls for heating, terminal W1 is ener- gized. In order to prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor is then energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited and the damper moves to the minimum position. If the accessory two-position damper is used, the outdoor-air damper opens to the minimum position whenever the evaporator fan runs. When additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the
thermostat is satisfied and W1 and W2 are deenergized, the IFM stops after a 45-second time-off delay. The economizer damper then moves to the fully closed position. When using continuous fan, the damper will remain in the minimum position.
OPERATING SEQUENCE FOR 581B036-150 SIZE UNITS
Units With Perfect Humidity™ Dehumidification Package — When thermostat calls for cooling, terminals G and Y1 is ener- gized. The indoor (evaporator) fan motor (IFM), compressor (C), and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. As shipped from the factory, Perfect Humidity dehumidification circuit is always ener- gized. If Perfect Humidity circuit modulation is desired, a field- installed, wall-mounted LC Thermidistat or humidistat are required.
If the Perfect Humidity humidistat is installed and calls for the Perfect Humidity subcooler coil to operate, the humidistat inter- nal switch closes. This energizes and closes the liquid line sole- noid valve coil (LLSV) of the Perfect Humidity circuit, forcing the hot liquid refrigerant of the liquid line to enter the subcooler coil. As the hot liquid passes through the subcooler coil, it is exposed to the cold supply airflow coming off from the evapora- tor coil and the liquid is further cooled to a temperature approaching the evaporator coil leaving-air temperature. The state of the refrigerant leaving the subcooler coil is a highly sub- cooled liquid refrigerant. The liquid then enters a thermostatic expansion valve (TXV) where the liquid is dropped to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid. The TXV can throttle the pressure drop of the liquid refrigerant and maintain proper conditions at the compressor suction valve over a wide range of operating conditions. The liquid then enters a second fixed restrictor expansion device for a second pressure drop to a 2-phase fluid. The liquid proceeds to the evaporator coil at a temperature lower than normal cooling operation. This lower temperature is what increases the latent capacity of the rooftop. The 2-phase refrigerant passes through the evaporator and is changed into a vapor. The air passing over the evaporator coil will become colder than during normal operation as a result of the colder refrigerant temperatures. However, as it passes over the subcooler coil, the air will be warmed slightly.
As the refrigerant leaves the evaporator, the refrigerant passes a low-pressure switch in the suction line. This low-pressure switch will deactivate the Perfect Humidity package when the suction pressure reaches 60 psig. The low-pressure switch is an added safety device to protect against evaporator coil freeze-up. The low-pressure switch will only deactivate and open the liquid line solenoid valve in the Perfect Humidity circuit. The compressors will continue to run as long as there is a call for cooling, regardless of the position of the low-pressure switch. The solenoid valve and the Perfect Humidity package will be re-activated only when the call for cooling has been sat- isfied, the low-pressure switch has closed, and a new call for cooling exists. The crankcase heaters on the scroll compressor provide additional protection for the compressor due to the additional refrigerant charge in the subcooler.
When the humidistat is satisfied, the humidistat internal switch opens cutting power to and opening the LLSV. The refrigerant is routed back through the evaporator and the subcooler coil is removed from the refrigerant loop.
When the thermostat is satisfied, C1 is deenergized and the compressor and OFM shut off. After a 30-second delay, the IFM shuts off. If the thermostat fan selector switch is in the ON posi- tion, the IFM will run continuously.