TYPICAL WIRING SCHEMATIC (cont)
(208/230 V 3-Phase Unit Shown) (cont)
|
|
| LEGEND |
AHA | — Adjustable Heat Anticipator | IFM | — Indoor (Evaporator) Fan Motor |
C | — Contactor, Compressor | IGC | — Integrated Gas Unit Controller |
CAP | — Capacitor | LED | — |
CC | — Cooling Compensator | LPS | — |
CLO | — Compressor Lockout | LS | — Limit Switch |
COMP | — Compressor Motor | MGV | — Main Gas Valve |
D | — Diode | MTR | — Motor |
EC | — Enthalpy Control | OAT | — |
ECON | — Economizer | OFM | — Outdoor (Condenser) Fan Motor |
EPS | — Emergency Power Supply | OLR | — Overload |
EQUIP | — Equipment | P | — Plug |
ER | — Economizer Relay | PL | — Plug Assembly |
FPT | — | QT | — Quadruple Terminal |
FSS | — | R | — Relay |
FU | — Fuse | RS | — Rollout Switch |
GND | — Ground | SAT | — |
GVR | — Gas Valve Relay | SEN | — Sensor |
HPS | — | SW1 | — Switch Fully Open |
HS | — | SW2 | — Switch Fully Closed |
HV | — High Voltage | SW3 | — Switch Minimum Vent Position |
I | — Ignitor | SW4 | — Switch Maximum Vent Position |
IDM | — | TC | — |
IFC | — Indoor (Evaporator) Fan Contactor |
|
|
TH —
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES:
1.If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
2.
3.Thermostats: HH07AT170, 172
Subbase: HH93AZ176, 177, 178 and 179
4.Set heat anticipator at .14 amp for first stage and .14 amp for second stage.
5.Use copper conductors only.
6.TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.