ELECTRICAL DATA (cont)

581B090-150 STANDARD MOTOR (Units Without Electrical Convenience Outlet)

 

NOMINAL

VOLTAGE

 

 

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

COMPRESSOR

OFM

IFM

SUPPLY

DISCONNECT

VOLTAGE

RANGE

FAN MOTOR

581B

 

 

 

 

WITH OUTLET

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP

FLA

 

LRA

 

 

 

 

208/230-3-60

187

254

12.4

88.0

1.4

7.5

.57

38.2/38.2

45/45†

40/40

 

242/242

090

460-3-60

414

508

6.4

44.0

0.7

3.4

.30

19.2

25†

20

 

121

 

575-3-60

518

632

4.8

34.0

0.7

3.4

.30

14.6

20†

16

 

95

 

208/230-3-60

187

254

15.0

99.0

1.4

7.5

.57

44.1/44.1

50/50†

46/46

 

264/264

102

460-3-60

414

508

8.2

49.5

0.7

3.4

.30

23.3

30†

24

 

132

 

575-3-60

518

632

5.8

40.0

0.7

3.4

.30

16.9

20†

18

 

107

 

208/230-3-60

187

254

18.9

125.0

1.4

10.6

.57

55.9/55.9

60/60†

59/59

 

341/341

120

460-3-60

414

508

9.0

62.5

0.7

4.8

.30

26.5

30†

28

 

171

 

575-3-60

518

632

7.1

50.0

0.7

4.8

.30

20.9

25†

22

 

136

 

208/230-3-60

187

254

19.0

156.0

1.4

15.0

.57

60.6/60.6

70/70

64/64

 

426/426

150

460-3-60

414

508

9.0

70.0

0.7

7.4

.30

29.1

35†

31

 

197

 

575-3-60

518

632

7.4

54.0

0.7

7.4

.30

23.7

30†

25

 

154

581B090-150 STANDARD MOTOR (Units With Electrical Convenience Outlet)

 

NOMINAL

VOLTAGE

 

 

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

COMPRESSOR

OFM

IFM

SUPPLY

DISCONNECT

VOLTAGE

RANGE

FAN MOTOR

581B

 

 

 

 

WITH OUTLET

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP

FLA

 

LRA

 

 

 

 

208/230-3-60

187

254

12.4

88.0

1.4

7.5

.57

44.2/44.2

50/50†

46/46

 

247/247

090

460-3-60

414

508

6.4

44.0

0.7

3.4

.30

21.9

25†

23

 

124

 

575-3-60

518

632

4.8

34.0

0.7

3.4

.30

16.8

20†

18

 

97

 

208/230-3-60

187

254

15.0

99.0

1.4

7.5

.57

50.1/50.1

60/60†

52/52

 

269/269

102

460-3-60

414

508

8.2

49.5

0.7

3.4

.30

26.0

30†

27

 

135

 

575-3-60

518

632

5.8

40.0

0.7

3.4

.30

19.1

25†

20

 

109

 

208/230-3-60

187

254

18.9

125.0

1.4

10.6

.57

61.9/61.9

70/70

64/64

 

345/345

120

460-3-60

414

508

9.0

62.5

0.7

4.8

.30

29.2

35†

30

 

173

 

575-3-60

518

632

7.1

50.0

0.7

4.8

.30

23.1

25†

24

 

139

 

208/230-3-60

187

254

19.0

156.0

1.4

15.0

.57

66.6/66.6

80/70

70/70

 

430/430

150

460-3-60

414

508

9.0

70.0

0.7

7.4

.30

31.8

35†

33

 

199

 

575-3-60

518

632

7.4

54.0

0.7

7.4

.30

25.9

30†

27

 

156

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker per NEC.

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the overcur-

rent protective device for the unit shall be fuse or HACR breaker. The

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

UL, Canadian approved units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

% Voltage Imbalance = 100 x

7

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percent

of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

47