The table below describes the faults that can be displayed during the automatic test.

TEST FAULT

DESCRIPTION

 

 

1

Outdoor air thermistor outside range

2

Outdoor air value read not validated by operator

 

 

3

Low pressure transducer, circuit A, outside range

4

High pressure transducer, circuit A, outside range

5

Low pressure transducer, circuit B, outside range

6

High pressure transducer, circuit B, outside range

 

 

7

Defrost thermistor, circuit A, outside range

8

Defrost thermistor, circuit B, outside range

 

 

9

Water flow switch not open

 

 

10

Primary pump not started or water flow switch not

 

closed

11, 12, 13; 14, 15

Water entering temperature sensor outside range

16, 17, 18, 19, 20

Water leaving temperature sensor outside range

21

Temperature difference between entering and leaving

 

water sensors too high

 

 

22, 23; 24, 25, 26

Water system leaving temperature sensor outside

 

range

 

 

27

Temperature difference between the system entering

 

and leaving water sensors too high

 

 

28

Water flow switch not closed or primary pump not

 

stopped

 

 

29

Secondary pump not started or water flow switch not

 

closed

 

 

30

Water flow switch not closed or secondary pump not

 

stopped

 

 

31

Command fault; compressor A1

32

Command fault; compressor A2

33

Command fault; compressor A3

34

Command fault, 4-way reversing valve, circuit A

 

 

35

Command fault; compressor B1

36

Command fault; compressor B2

37

Command fault; compressor B3

 

 

38

Command fault, 4-way reversing valve, circuit B

 

 

39

Low-speed test, fan A1 not validated by the operator

40

High-speed test, fan A1 not validated by the operator

41

Low-speed test, fan B1 not validated by the operator

42

High-speed test, fan B1 not validated by the operator

43

Test fan A2 not validated by the operator

44

Test fan B2 not validated by the operator

45

Water heat exchanger heater and air heat exchanger

 

condensate heater test, circuit A not validated by the

46

operator

 

Air heat exchanger condensate heater, circuit B, not

 

validated by the operator

 

 

47

Boiler activation test not validated by the operator

 

 

48

Electric heating stage 1 activation test not validated

 

by the operator

49

Electric heating stage 2 activation test not validated

 

by the operator

50

Electric heating stage 3 activation test not validated

 

by the operator

51

Electric heating stage 4 activation test not validated

 

by the operator

 

 

52

Alarm relay output activation test, circuit A not

 

validated by the operator

53

Alarm relay output activation test, circuit B not

 

validated by the operator

 

 

4.3.11- Description of the configuration menu

4.3.11.1- General

This menu can be used to display and modify all configura- tions: Factory, Service and User. Only the User Configuration can be modified by the end-user. The Factory, Service and master/ slave configurations are not described in this document. A configuration can only be modified if the unit is fully stopped (LOFF).

The menus User 1 [USEr 1] and User 2 [USEr 2] are pass- word-protected. The other menus are directly accessible, except if item 11 of the User 2 menu (password for all con- figurations) has been validated.

4.3.11.2 - Password

A password must be entered in order to access the test function or to modify a configuration. It is automatically requested, if necessary: 'EntEr PASS' is displayed on the 4-digit display and the configuration menu LED flashes, indicating that the modification mode is active. Press the arrow keys until the value '11' is displayed on the 4-digit display. Press Enter to validate this. The configuration menu LED stops flashing. If the password is correct, 'Good' is displayed. If the password is incorrect, 'PASS incorrEct' is displayed. The User password has a default value of 11.

This value can be modified through the Service configuration. The password can be entered if the unit is fully stopped, otherwise 'ACCES dEniEd' (access denied) will be displayed on the 4-digit display. The controller automatically deactivates the password after 5 minutes without activity (i.e. no buttons pressed) or after powering up.