The table below describes the faults that can be displayed during the automatic test.
TEST FAULT | DESCRIPTION |
|
|
1 | Outdoor air thermistor outside range |
2 | Outdoor air value read not validated by operator |
|
|
3 | Low pressure transducer, circuit A, outside range |
4 | High pressure transducer, circuit A, outside range |
5 | Low pressure transducer, circuit B, outside range |
6 | High pressure transducer, circuit B, outside range |
|
|
7 | Defrost thermistor, circuit A, outside range |
8 | Defrost thermistor, circuit B, outside range |
|
|
9 | Water flow switch not open |
|
|
10 | Primary pump not started or water flow switch not |
| closed |
11, 12, 13; 14, 15 | Water entering temperature sensor outside range |
16, 17, 18, 19, 20 | Water leaving temperature sensor outside range |
21 | Temperature difference between entering and leaving |
| water sensors too high |
|
|
22, 23; 24, 25, 26 | Water system leaving temperature sensor outside |
| range |
|
|
27 | Temperature difference between the system entering |
| and leaving water sensors too high |
|
|
28 | Water flow switch not closed or primary pump not |
| stopped |
|
|
29 | Secondary pump not started or water flow switch not |
| closed |
|
|
30 | Water flow switch not closed or secondary pump not |
| stopped |
|
|
31 | Command fault; compressor A1 |
32 | Command fault; compressor A2 |
33 | Command fault; compressor A3 |
34 | Command fault, |
|
|
35 | Command fault; compressor B1 |
36 | Command fault; compressor B2 |
37 | Command fault; compressor B3 |
|
|
38 | Command fault, |
|
|
39 | |
40 | |
41 | |
42 | |
43 | Test fan A2 not validated by the operator |
44 | Test fan B2 not validated by the operator |
45 | Water heat exchanger heater and air heat exchanger |
| condensate heater test, circuit A not validated by the |
46 | operator |
| Air heat exchanger condensate heater, circuit B, not |
| validated by the operator |
|
|
47 | Boiler activation test not validated by the operator |
|
|
48 | Electric heating stage 1 activation test not validated |
| by the operator |
49 | Electric heating stage 2 activation test not validated |
| by the operator |
50 | Electric heating stage 3 activation test not validated |
| by the operator |
51 | Electric heating stage 4 activation test not validated |
| by the operator |
|
|
52 | Alarm relay output activation test, circuit A not |
| validated by the operator |
53 | Alarm relay output activation test, circuit B not |
| validated by the operator |
|
|
4.3.11- Description of the configuration menu
4.3.11.1- General
This menu can be used to display and modify all configura- tions: Factory, Service and User. Only the User Configuration can be modified by the
The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-
4.3.11.2 - Password
A password must be entered in order to access the test function or to modify a configuration. It is automatically requested, if necessary: 'EntEr PASS' is displayed on the
This value can be modified through the Service configuration. The password can be entered if the unit is fully stopped, otherwise 'ACCES dEniEd' (access denied) will be displayed on the