PARAMETER STATUS

ON/OFF

CONTROL

HEATING/COOLING

REMOTE HEATING/

HC_SEL

OUTDOOR TEMPERATURE

OPERATING

STATUS

TYPE

SELECTION IN

COOLING CONTACTS

 

 

MODE

 

 

LOCAL MODE

 

 

 

 

 

 

 

 

 

 

 

Off

-

-

-

-

-

Cooling

 

 

 

 

 

 

 

On

Local

Cooling

-

-

-

Cooling

 

 

 

 

 

 

 

On

Local

Heating

-

-

-

Heating

 

 

 

 

 

 

 

On

Local

Auto

-

-

> Cooling threshold

Cooling

 

 

 

 

 

 

 

On

Local

Auto

-

-

< Heating threshold

Heating*

 

 

 

 

 

 

 

On

Local

Auto

-

-

Between cooling and heating thresholds

Standby

 

 

 

 

 

 

 

On

Remote

-

Cooling mode

-

-

Cooling

 

 

 

 

 

 

 

On

Remote

-

Heating mode

-

-

Heating

 

 

 

 

 

 

 

On

Remote

-

Auto mode

-

> Cooling threshold

Cooling

 

 

 

 

 

 

 

On

Remote

-

Auto mode

-

< Heating threshold

Heating*

On

Remote

-

Auto mode

-

Between cooling and heating thresholds

Standby

On

CCN

-

-

Cooling

-

Cooling

On

CCN

-

-

Heating

-

Heating

On

CCN

-

-

Auto

> Cooling threshold

Cooling

 

 

 

 

 

 

 

On

CCN

-

-

Auto

< Heating threshold

Heating*

 

 

 

 

 

 

 

On

CCN

-

-

Auto

Between cooling and heating thresholds

Standby

 

 

 

 

 

 

 

*Does not apply to cooling only units that do not control a boiler.

5.3 - Evaporator water pump control

The unit can control one or two evaporator water pumps. The evaporator water pump is turned on when this option is configured (see User configuration) and when the unit is in one of the on modes described above or in delay mode. Since the minimum value for the delay at start-up is 1 minute (configurable between 1 and 15 minutes), the pump will run for at least one minute before the first compressor starts. The pump is kept running for 20 seconds after the unit goes to stop mode. The pump keeps working when the unit switches from heating to cooling mode or vice-versa. It is turned off if the unit is shut down due to an alarm unless the fault is a frost protection error. The pump can be started in particular operating conditions when the evaporator heater is active (see section 5.5). See section 5.14 for the particular evaporator pump control for the follower unit (master/slave assembly).

If two pumps are controlled and the reversing function has been selected (see User 1 configuration), the control tries to limit the pump run time delta to the configured pump change- over delay. If this delay has elapsed, the pump reversing function is activated, when the unit is running. During the reversing function both pumps run together for two seconds.

If a pump has failed and a secondary pump is available, the unit is stopped and started again with this pump.

The control provides a means to automatically start the pump each day at 14.00 hours for 2 seconds when the unit is off. If the unit is fitted with two pumps, the first pump is started on odd days and the second pump is started on even days. Starting the pump periodically for few seconds increases the life-time of the pump bearings and the tightness of the pump seal.

5.4 - Control interlock contact

This contact checks the status of a loop (water flow switch and customer safety loop, see section 3.6). It prevents the unit from starting if it is open when the delay at start-up has expired. This open contact leads to an alarm shut-down, if the unit is running.

5.5 - Evaporator antifreeze protection

The heater for the evaporator and water pump cycling (for units with a pump) can be energised to protect the evaporator, if it can be damaged by freezing, when the unit is shut down for a long time at low outdoor temperature.

NOTE: Evaporator heater control parameters can be modified, using the Service configuration.

5.6 - Control point

The control point represents the water temperature that the unit must produce. The inlet water is controlled by default, but the outlet water can also be controlled (requires a Service configuration modification).

Control point = active setpoint + reset

5.6.1 - Active setpoint

Two setpoints can be selected as active in cooling mode and three in heating mode. Usually, the second cooling setpoint is used for unoccupied periods or for ice storage (brine unit). The second setpoint in heating mode is used for unoccupied periods, and the third heating setpoint is used for holiday periods or public holidays. Depending on the current opera- tions, the active setpoint can be selected by choosing the item in the Information menu, with the user’s volt-free contacts, with network commands or with the setpoint timer program (schedule 2).

31

Page 31
Image 31
Carrier 30RY/RYH Evaporator water pump control, Control interlock contact, Evaporator antifreeze protection, Control point

30RY/RYH, 30RA/RH specifications

The Carrier 30RY/RYH and 30RA/RH chiller models are leading solutions in commercial and industrial cooling applications. Renowned for their reliability, efficiency, and advanced technologies, these chillers cater to a wide variety of settings, from office buildings to manufacturing facilities.

The 30RY/RYH series features a distinctive design optimized for performance, utilizing a centrifugal compressor that ensures smooth operation under varying loads. One of the standout features of these chillers is their high-efficiency capabilities, which contribute to lower energy consumption. The models are engineered to deliver substantial energy savings, meeting or exceeding the latest ASHRAE and DOE efficiency standards.

A significant aspect of the 30RY and 30RA models is their use of environmentally friendly refrigerants. The 30RYH, for instance, employs R-134a refrigerant, which is designed to minimize ozone depletion while maximizing efficiency. This commitment to sustainability aligns with modern environmental regulations and practices, making these chillers a wise choice for eco-conscious projects.

In terms of control technology, the chiller models come equipped with advanced microprocessor-based controls, providing users with optimal system management and diagnostics. This integrated control system enhances the overall performance and reliability of the chillers, allowing for real-time monitoring and adjustment to ensure peak operational efficiency.

Another key feature is the quiet operation of the 30RY/RYH and 30RA/RH series. Designed with sound attenuation in mind, these units minimize noise pollution, making them suitable for installations in noise-sensitive environments. Additionally, the modular design allows for easy installation and maintenance, reducing downtime and providing flexibility in system design.

Both series also offer robust thermal performance, with the capability to handle a wide range of operating conditions. The chillers excel in terms of cooling capacity, providing solutions for varying thermal loads while maintaining energy efficiency. This adaptability is invaluable for facilities managing seasonal changes in cooling demands.

In summary, the Carrier 30RY/RYH and 30RA/RH chillers represent an ideal blend of efficiency, advanced technology, and eco-friendliness. Their high-performance capabilities, user-friendly controls, and sustainable design make them a top choice for commercial and industrial applications, ensuring dependable cooling solutions for diverse environments.