Carrier 30RA/RH, 30RY/RYH manual ALARM CODE DESCRIPTIONS continued

Models: 30RY/RYH 30RA/RH

1 36
Download 36 pages 61.05 Kb
Page 36
Image 36
ALARM CODE DESCRIPTIONS (continued)

ALARM CODE DESCRIPTIONS (continued)

ALARM

ALARM NAME

ALARM DESCRIPTION

ACTION TAKEN BY

RESET TYPE

PROBABLE CAUSE

CODE

 

 

THE CONTROL

 

 

30

Low refrigerant pressure failure,

Circuit running and the suction pressure

Circuit shut down

Automatic when pressure returns to

Shortage of refrigerant, filter blocked or

 

circuit A

below threshold

 

normal and if the same fault has not

faulty pressure sensor

 

 

 

 

occurred the same day (machine

 

 

 

 

 

equipped with CCN/clock board, If not,

 

 

 

 

 

manual)

 

31

Low refrigerant pressure failure,

As above

As above

As above

As above

 

circuit B

 

 

 

 

32

High pressure failure, circuit A

Circuit running and the discharge pressure

Circuit shut down

Manual, the high pressure switch must

Fan circuit fault, high condenser

 

 

exceeds the high pressure trip point

 

be reset manually with the push-button

entering air temperature

 

 

 

 

located on or in the pressure switch

 

33

High pressure failure, circuit B

As above

As above

As above

As above

34

Reverse compressor rotation,

One circuit compressor runs in reverse

As above

As above

Incorrect compressor wiring

 

circuit A

rotation

 

 

 

35

Reverse compressor rotation,

As above

As above

As above

As above

 

circuit B

 

 

 

 

36

Water heat exchanger frost

The heat exchanger entering or leaving

Unit shut down

Automatic if the same alarm has not

Low water flow or defective thermistor

 

protection

water sensor is below the frost trip point

 

tripped the same day (machine equipped

 

 

 

 

 

with CCN/clock board, If not, manual)

 

37

Repeated low evaporator

More than 6 successive circuit capacity

Circuit shut down

Manual

Faulty pressure sensor, clogged filter or

 

suction temperature unloading,

unloads because of low suction temperature

 

 

low refrigerant charge

 

circuit A

override.

 

 

 

38

Repeated low evaporator suction

As above

As above

As above

As above

 

temperature unloading, circuit B

 

 

 

 

39

Repeated high pressure

More than 6 successive circuit capacity

None

Automatic

Faulty transducer, high condenser

 

unloading, circuit A

unloads because of high pressure override.

 

 

entering air temperature, high entering

 

 

 

 

 

water temperature, condenser fouled

 

 

 

 

 

fan flow rate too low.

40

Repeated high pressure

As above

As above

As above

As above

 

unloading, circuit B

 

 

 

 

41

Repeated high discharge

More than 8 successive circuit capacity

As above

As above

Pressure sensor faulty or heat

 

temperature unloading in

unloads because of high discharge

 

 

exchanger fouled

 

heating mode, circuit A

temperature

 

 

 

42

Repeated high discharge

As above

As above

As above

As above

 

temperature unloading in

 

 

 

 

 

heating mode, circuit B

 

 

 

 

43

Repeated low suction

More than 8 successive circuit capacity

As above

As above

Pressure sensor faulty, filter obstructed,

 

temperature unloading in

unloads because of low suction temperature

 

 

shortage of refrigerant, heat exchanger

 

heating mode, circuit A

 

 

 

fouled or fan faulty.

44

Repeated low suction

As above

As above

As above

As above

 

temperature unloading in

 

 

 

 

 

heating mode, circuit B

 

 

 

 

45

Low heat exchanger entering

Heat exchanger temperature is too low (less

Unit shut down

As above

As above

 

water temperature in heating

than 10°C), preventing unit start-up

 

 

 

 

mode

 

 

 

 

46

Safety interlock open

Safety interlock not closed before end of the

Unit prevented to start

Manual

Evaporator pump control or water flow

 

 

start-up delay or opens during operation

or shut down

 

switch failure

47

Pump #1 fault

Evap. water pump run contact opens while

Unit shut down

Manual

Pump overheat, incorrect pump

 

 

the pump has received a command to be on

 

 

connection

48

Pump #2 fault

As above

Unit shut down

Manual

As above

49

CCN emergency stop

CCN command received to shutdown the

Unit shut down

Manual

Network command

 

 

unit

 

 

 

50

Loss of communication with

The unit is controlled by a System Manager

Unit returns to

Automatic when communication is re-

Defective CCN bus wiring or system

 

System Manager

and communication with this module is lost

autonomous operating

established

module failure

 

 

for more than 2 minutes

mode

 

 

51

Communication failure with the

The master/slave link is broken due to a

As above

As above

As above

 

master or the slave unit

loss of communication between the two

 

 

 

 

 

units for more than 2 minutes

 

 

 

52

Initial factory configuration

All factory parameters are zero

Unit prevented to start

Automatic

No factory configuration

 

required

 

 

 

 

 

 

 

 

 

 

53

Illegal factory configuration

Wrong factory configuration

As above

Automatic

Factory configuration error

54

Master/slave configuration error

Wrong master/slave configuration

Master/slave control

Automatic

Master or slave configuration error

 

 

 

disabled

 

 

 

Maintenance alerts

A maintenance alert is active

None

Manual

 

55-2

Water loop flow rate too low

 

 

 

 

55-4

Maintenance delay, pump 1,

 

 

 

 

 

elapsed

 

 

 

 

55-5

Maintenance delay, pump 2,

 

 

 

 

 

elapsed

 

 

 

 

55-6

Maintenance delay, water filter,

 

 

 

 

 

elapsed

 

 

 

 

 

 

 

 

 

 

Order No. 13444-76, 06.2005. Supersedes order No.: 13429-76, 06.2004. Manufacturer reserves the right to change any product specification without notice.

Manufactured by: Carrier s.a., Montluel, France. Printed in the Netherlands on chlorine-free paper.

Page 36
Image 36
Carrier 30RA/RH, 30RY/RYH manual ALARM CODE DESCRIPTIONS continued