USER 1 CONFIGURATION SUB-MENU [2]

4.3.11.3 - Description of the User 1 Configuration sub-menu

USER 1 CONFIGURATION SUB-MENU [2]

ITEM

FORMAT

UNITS

DEFAULT

COMMENTS

0

USEr MEnu

-

-

When selected this item authorises return to the previous menu.

2 [1]

YES/no

-

no

Ramp loading select. For units with more than one compressor only.

 

 

 

 

Yes = ramp enabled

 

 

 

 

No = ramp disabled

 

 

 

 

This configuration enables the ramp to be activated for heating or cooling (depending on configuration): the

 

 

 

 

maximum rate (in °C/min) of temperature drop or rise for the heat exchanger water (leaving or entering, upon

 

 

 

 

configuration). Ramp setting value can be configured in the Setpoint menu.

3

1 to 15

min

1

Delay at start-up. This value is reinitialised after power-up or when both circuits are halted by local, remote or

 

 

 

 

CCN command. No compressor will be started up until this pause has expired. However, the evaporator pump

 

 

 

 

command will be activated immediately. The safety lockout loop will not be checked until the pause has

 

 

 

 

expired.

4

0/1/2/3/4

-

0

Pump sequence select

 

 

 

 

0 = no pump

 

 

 

 

1 = one pump only

 

 

 

 

2 = two pumps with auto rotation

 

 

 

 

3 = pump #1 manual select

 

 

 

 

4 = pump #2 manual select

 

 

 

 

If the auto sequence is selected, the pump change-over occurs when the rotation delay is elapsed. If the

 

 

 

 

manual sequence is selected then, the selected pump is used in priority. Change-over occurs if one pump fails.

 

 

 

 

 

5 [1]

24 to 3000

hours

48

Pump changeover delay. Displayed if auto pump sequence is selected. This parameter is used for pump

 

 

 

 

auto-rotation: the control tries to limit the pump run time difference to the pump changeover delay value.

 

 

 

 

Change-over between pumps occurs when this difference becomes greater than the configured pump

 

 

 

 

changeover delay.

6 [1]

«YES/no»

-

noi

Pump shutdown in standby mode

 

 

 

 

Displayed if the unit controls a water pump. If this parameter is validated, the pump will be shut down when

 

 

 

 

the standby mode is active (in automatic heating/cooling changeover). It automatically restarts in heating or

 

 

 

 

cooling mode.

7 [1]

0/1

-

0

Contact 3 select (for single-circuit units)

 

 

 

 

0 = input is used for demand limit command control

 

 

 

 

1 = input is used for dual setpoint command control

 

 

 

 

Determines whether contact 3 is used for remote demand limit or dual setpoint control. For single-circuit units

 

 

 

 

only.

8

0/1/2

-

0

Cooling setpoint reset select. See section 5.6.2.

 

 

 

 

0 = reset not selected

 

 

 

 

1 = reset based on outdoor temperature

 

 

 

 

2 = reset based on return water temperature

 

 

 

 

 

9 [1]

0/1/2

-

0

Heating setpoint reset select. See section 5.6.2

 

 

 

 

0 = reset not selected

 

 

 

 

1 = reset based on outdoor temperature

 

 

 

 

2 = reset based on return water temperature

 

 

 

 

 

10

«YES/no»

-

no

Boiler control select

 

 

 

 

Yes = boiler controlled by the unit

 

 

 

 

No = boiler not controlled

11 [1]

-15 to 0

°C

-10

Boiler threshold. Outdoor air temperature limit; if the temperature is lower, the heat pump is stopped or only

 

 

 

 

the boiler is used for hot water production. Only for heat pumps controlling an additional boiler.

12 [1]

-20 to 0

°C

-15

Operating threshold, heating mode. Outside air temperature threshold below which the heat pump shuts

 

 

 

 

down. The unit switches the electric heaters on and off (if these exist). For heat pumps only.

13 [1]

-5 to 21

°C

5

Electric heating stage threshold. Maximum outdoor air temperature threshold for the use of electric heating

 

 

 

 

stages. Only for heat pumps, equipped with optional additional electric heating stages.

14 [1]

«YES/no»

-

no

Electric heating safety stage. In this configuration the last electric heating stage is only activated in the safety

 

 

 

 

mode (in case of a unit fault that prevents unit operation in heat pump mode).The other electric heating stages

 

 

 

 

operate normally. See section 5.12.

 

 

 

 

 

15 [1]

0 to 60

minutes

 

Electric heating stage operation schedule. Permits configuration of a start-up delay after unit start-up during

 

 

 

 

which the electric heater stages are not allowed to start.

16 [1]

«YES/no»

-

no

Quick start-up, electric heater stages in defrost mode. If a circuit switches to defrost mode, the electric

 

 

 

 

heater stages are allowed to start up immediately. For heat pumps only.

17 [1]

«YES/no»

-

no

Automatic cooling/heating changeover select. Permits activation of the automatic changeover function.

 

 

 

 

Caution: This function requires a special operation for control contacts 1 and 2, if the machine is under remote

 

 

 

 

control (see section 3.6.3).

 

 

 

 

 

18

«YES/no»

-

yes

Extended menu select

 

 

 

 

Yes = menu description available

 

 

 

 

No = menu description not available

 

 

 

 

This item authorises activating or inhibiting the menu item expanded display.

1This item shall be masked when not used.

2Access to menu is read/write.