If the automatic heating/cooling changeover function is not selected (see sections 4.3.11.3, 5.1 and 5.2) the operation of contacts 1 and 2 is as follows:

3.6.2- Volt-free contact on/off/cooling/heating without multiplexing

If the automatic heating/cooling changeover function is not selected (see sections 4.3.11.3, 5.1 and 5.2) the operation of contacts 1 and 2 is as follows:

 

OFF

ON cooling

ON heating

Contact 1

Open

Closed

Closed

Contact 2

-

Open

Closed

Contact status not significant

3.6.3- Volt-free contact on/off/cooling/heating with multiplexing

If the automatic heating/cooling changeover function is selected (see sections 4.3.11.3, 5.1 and 5.2) the operation of contacts 1 and 2 is multiplexed:

 

OFF

ON cooling

ON heating

ON auto

Contact 1

Open

Closed

Closed

Open

 

 

 

 

 

Contact 2

Open

Open

Closed

Closed

 

 

 

 

 

NOTE: The automatic changeover function (ON auto) selects the cooling or heating mode based on the outdoor temperature (see section 5.2).

3.6.4- Demand limit or setpoint volt-free contact for single- circuit units

On single-circuit units contact 3 determines the selection of demand limit or setpoint, based on the configuration (see User Configuration 1 menu).

Demand limit selection

Setpoint selection

100%

Limit 1

Setpoint 1

Setpoint 2

(no limit)

 

 

 

 

 

 

 

Contact 3 Open

Closed

Open

Closed

3.6.5- Demand limit volt-free contact for dual-circuit units On dual-circuit units the operation of the demand limit selection contacts is multiplexed. The demand limit setpoints are adjustable in the setpoint menu (see section 4.3.8).

 

100%

Limit 1

Limit 2

Limit 3

 

(no limit)

 

 

 

Contact 3

Open

Closed

Open

Closed

Contact 4

Open

Open

Closed

Closed

3.6.6- Water setpoint selection volt-free contact with multiplexing for dual-circuit units

On dual-circuit units the operation of the cold water or hot water setpoint selection contacts is multiplexed. The set-points are adjustable in the setpoint menu (see section 4.3.8). Auto means that the active setpoint is determined by the setpoint schedule (see section 5.6.1).

Cooling mode

 

Setpoint 1

Setpoint 2

Setpoint 3

Auto

Contact 5

Open

Open

Closed

Closed

Contact 6

Open

Closed

Open

Closed

 

 

 

 

 

Heating mode

 

 

 

 

 

 

 

 

 

 

Setpoint 1

Setpoint 2

Setpoint 3

Auto

 

 

 

 

 

Contact 5

Open

Open

Closed

Closed

Contact 6

Open

Closed

Open

Closed