4.3.10.3 - Manual tests

OUTPUTS STATUS & TESTS MENU [2] [3] continued

ITEM

FORMAT

UNITS

DESCRIPTION

13 [1]

b1b2b3b4

 

Additional heating stage status.

 

tESt

 

b1

= stage 1

 

 

 

b2

= stage 2

 

 

 

b3

= stage 3

 

 

 

b4 = stage 4

 

 

 

In test mode the arrow keys successively display 0001, 0010, 0100 and 1000 to force the status of each electric heating stage

 

 

 

in turn.

 

 

 

This item is only displayed for heat pump units controlling additional electric heater stages. See section 5.12.

 

 

 

 

14 [1]

YES

-

Used for local interface test only. Lights or flashes all LEDs and blocks, so as to check that they are working properly.

 

no

-

 

 

 

tESt

%

 

 

 

 

 

 

15

Auto tESt

-

Automatic test. Selecting this item activates the automatic test function.

 

 

 

 

 

1This item is displayed in certain unit configurations only.

2Testing authorised only if the unit is in Local Off and all compressors are off.

3Password needed only for testing.

“Test” Displayed in turn with the item value during tests.

4.3.10.3 - Manual tests

This function allows the user to test the outputs individually, if the machine is completely shut down (LOFF). To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key (longer than 2 seconds) to activate the modification mode. The password is automatically requested, if it has not previously been verified. The Outputs/Test LED on the user interface begins to flash. Enter the desired test value and again press Enter to start the test. 'TESt' is displayed on the 4- digit display alternately with the value tested. The Outputs/Test LED stops flashing. Press the Enter key or an arrow key to stop the test.

4.3.10.4 - Automatic tests

The automatic test function verifies the integrity of the analo- gue entries and activates the outputs in sequence. For each test 't XX' is displayed on the user interface. 'xx' indicates the number of the test in progress. When a test has been completed, the following test is automatically activated.

A message may appear, asking the operator for a validation with the Enter key, if the control cannot automatically verify a sensor value or an output status. If the value read or the output status is incorrect, the operator must press a different key (not the Enter key) to cancel the automatic test procedure.

If a test fails, an error message and an error code are dis- played. The automatic test procedure is interrupted.

When all tests have been completed, an end-of-test message appears.

The table below describes the messages shown on the user interface during the automatic test sequence.

TEXT

DESCRIPTION

Thermistor test failed [XX]

Test number XX of the thermistor has failed

Pressure test failed [XX]

Test number XX of the pressure sensor has

 

failed

 

 

Output test failed [XX]

Output test number XX has failed

 

 

Input test failed [XX]

Input test number XX has failed

 

 

Press enter if test [XX] correct

Request for the operator to validate test XX

 

 

OAT [value] press enter if

Request for the operator to validate the

test [XX] correct

outdoor air temperature value displayed.

 

Test number XX

Auto test completed

Automatic test completed