LEAVING WATER TEMPERATURE CONTROL
SETPOINT - °C | |
Minimum cooling value |
|
Water | 5.0 |
Medium brine | 0.0 |
Brine | |
Maximum cooling value | 20.0 |
Feedback setpoint, cooling | 6.0 |
Minimum heating value | 20.6 |
Maximum heating value | 56.1 |
Feedback setpoint heating | 48.0 |
| |
ENTERING WATER TEMPERATURE CONTROL | |
|
|
SETPOINT - °C | |
|
|
Minimum cooling value |
|
Water | 10.0 |
Medium brine | 6.1 |
Brine | |
Maximum cooling value | 26.1 |
Feedback setpoint, cooling | 12.0 |
Minimum heating value | 14.4 |
Maximum heating value | 50.0 |
Feedback setpoint heating | 42.0 |
RESET THRESHOLDS IN COOLING OR HEATING MODE
Reset threshold | Zero | Full |
Reset based on outdoor | ||
air temperature |
|
|
Reset based on | 0 to 11.1 °C | 0 to 11.1 °C |
Delta T |
|
|
|
|
|
4.3.9 - Description of the Inputs menu
INPUTS MENU [2]
ITEM | FORMAT | UNITS | COMMENTS |
|
|
|
0 | oPEn/CLoS | - | Remote contact 1 status. |
|
|
|
|
|
| If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to start and | |||
|
|
| stop the unit. If the auto cooling/heating changeover function is selected, this contact is multiplexed with contact 2 to | |||
|
|
| permit starting and stopping the unit and the selection of heating/cooling/auto. This contact is only valid, if the unit is in | |||
|
|
| the remote operating control (rEM) mode. See section 3.6 for the description of the connections of this contact. | |||
|
|
|
|
|
|
|
1 [1] | oPEn/CLoS | - | Remote contact 2 status. |
|
|
|
|
|
| If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to select the | |||
|
|
| heating or cooling mode. If the auto cooling/heating changeover function is selected, this contact is multiplexed with | |||
|
|
| contact 1 to permit starting and stopping the unit and the selection of heating/cooling/auto. This contact is only valid, if | |||
|
|
| the unit is in the remote operating control (rEM) mode. See section 3.6 for the description of the connections of this | |||
|
|
| contact. |
|
|
|
2 | oPEn/CLoS | - | Remote contact 3 status. |
|
|
|
|
|
| The operation of this contact depends on the unit type. |
|
| |
|
|
| ||||
|
|
| Configuration. If this contact is used for selecting a setpoint it is only active if the unit is in the remote operating control | |||
|
|
| mode. If the contact is used to limit the demand of the unit, it is active in all operating types. |
| ||
|
|
| Open contact: unit capacity is not limited or unit control is based on setpoint 1. |
| ||
|
|
| Closed contact: unit capacity is limited at limit setpoint 1 or unit control is based on setpoint 2. |
| ||
|
|
| See section 4.3.11.3 for the configuration of contact 3 - section 5.6.1 for the description of the setpoint selection - | |||
|
|
| section 5.7 for the description of the demand limit function and 3.6 for the description of the connection of contact 3 for | |||
|
|
|
|
|
| |
|
|
| ||||
|
|
| contact is active in all operating types. See section 3.6.5 for the description of this contact and section 5.7 for the | |||
|
|
| description of the demand limit function. |
|
|
|
|
|
|
|
|
|
|
3 | oPEn/CLoS | - | Remote contact 4 status. |
|
|
|
|
|
| This contact is only used for | |||
|
|
| demand limit value. This contact is active in all operating types. See section 3.6.5 for the description of this contact | |||
|
|
| and section 5.7 for the description of the demand limit function. |
|
| |
|
|
|
|
|
|
|
4 [1] | oPEn/CLoS | - | Remote contact 5 status. |
|
|
|
|
|
| This contact is only used for | |||
|
|
| setpoint. This contact is only active in the remote operating control mode. See section 3.6.6 for the description of this | |||
|
|
| contact and section 5.6.1 for the description of the setpoint selection function. |
| ||
5 [1] | oPEn/CLoS | - | Remote contact 6 status. |
|
|
|
|
|
| This contact is only used for | |||
|
|
| setpoint. This contact is only active in the remote operating control mode. See section 3.6.6 for the description of this | |||
|
|
| contact and section 5.6.1 for the description of the setpoint selection function. |
| ||
|
|
|
| |||
6 [1] | oPEn/CLoS | - | Interlock status. When this contact opens the unit stops or is prevented from starting and an alarm is created. This | |||
|
|
| contact is used to control the water flow. In addition, a customer safety device can be connected in series with this | |||
|
|
| contact (see section 3.6). |
|
|
|
7 | oPEn/CLoS | - | Water pump run contact status. When this contact opens while an evaporator pump has received a command to be | |||
|
|
| on then a pump failure alarm is tripped. |
|
|
|
8 [1] | b1b2b3 | - | Compressor feedback contacts, circuit A | b1 = feedback A1 | b2 = feedback A2 | b3 = feedback A3 |
9 [1] | b1b2b3 | - | Compressor feedback contacts, circuit B | b1 = feedback B1 | b2 = feedback B2 | b3 = feedback B3 |