Table 14 — VFD Mode Summary for 50XJ Unit

KEY OPERATON

LED MESSAGE

EXPLANATION

0.0

Standard monitor mode

S/P/M

SEtP

Switch to mode selection menu.

S/P/M

PrG

Program mode.

S/P/M

non

Select Status Monitor mode title with U/D keys.

R/W

Fr-F

Enter Status Monitor mode by pressing R/W. First monitor

 

 

item (motor run direction) is displayed.

DOWN

60.0

Pressing UP/DOWN views next/previous status variable.

 

 

Frequency command value displayed (monitor #1)

DOWN

C 0

Load current (%) monitor (monitor #2)

DOWN

Y 228

Input voltage (V) monitor (monitor #3)

DOWN

P 0

Output voltage (V) monitor (monitor #4)

DOWN

A....

Input terminal status monitor

DOWN

b....

Input terminal status monitor

DOWN

O....

Output terminal status monitor

DOWN

t0.00

Total RUN time monitor

DOWN

OC1

Past trip #1 monitor

DOWN

OC2

Past trip #2 monitor

DOWN

OC3

Past trip #3 monitor

DOWN

nErr

Past trip #4 monitor

DOWN

Fr-F

Return to the top menu item

50BV Variable Frequency Drive Control — The variable frequency drive is factory wired and programmed for proper operation with the unit controls; no installation or service adjustments are normally required.

The VFD default conditions at unit power up are: “0.0 Hz” in the LED display. When the fan is operating, the LED displays the output frequency in Hz.

OPERATING KEYPAD — The keypad allows users to en- able or disable the keypad, input commands from the keypad, and monitor drive operation. Fig. 7 shows the operating panel keypad layout and the locations of the keys and display LEDs.

The 4-character LED displays various values, depending upon what mode is running.

In Standard Monitor mode: the LED displays the current output frequency.

In Status Monitor mode: monitors the status conditions and frequency command value setting.

In Setup mode: displays setup parameter titles and values.

During a trip: displays the trip title.

The appropriate local/remote LED, which is inset into the speed control key, is lit when the unit is in local or remote mode.

KEY FUNCTIONS — Refer to Fig. 8 for the functions of each key on the keypad.

NON-TRIP MESSAGES — Non-trip messages are those that may be displayed but do not cause a trip and are not recorded in the fault history. Table 15 lists the non-trip messages with their explanations.

TRIP MESSAGES — Trip messages and their causes are shown in Table 16.

CLEARING A TRIP — A trip clear can be performed after the cause of the trip has been removed. To perform a trip clear, either switch off power to the inverter (keep VFD off until charge LED turns off) or use the following procedure:

Press STOP. The display will show: CLr. Press STOP again. The display will show: 0.0, indicating that the trip is cleared and the display will return to Standard Monitor mode.

If any key other than the STOP key is pressed at the trip clear command prompt, the trip clear command is aborted and the display returns to Standard Monitor mode (where the trip title will be displayed flashing). The trip clear command does not clear the recorded past faults.

STATUS MONITOR MODE — In Status Monitor mode, it is possible to monitor the inverter status (frequency command, output voltage, current, terminal information, etc.). Status monitor mode is entered by pressing the MON key until the monitor LED is lit. The present output frequency (which, just after power is applied, is 0.0) is displayed. (If the ST-CC terminals are not shorted, OFF will be displayed.)

If either or is pressed continuously, every 0.5 sec the next/previous item will be displayed. As optional points, RUN, STOP, displaying the frequency status, and switching to local/remote and manual/auto modes can be performed.

22

Page 22
Image 22
Carrier 50XJ064-104 specifications VFD Mode Summary for 50XJ Unit, KEY Operaton LED Message Explanation, Down

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.