Configuration Screens (cont)

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::DOPI_01: Supply Fan Status

 

 

 

Discrete Output Point

SFS

 

Name

Time Schedule

OCCPC01

 

Name

Setpoint Schedule

SETPT01

 

Name

Permissive Interlock

 

 

 

Control Point Type

Analog

 

Type

Occ Discrete State

On

 

OccSt

Unocc Discrete State

On

 

UnoccSt

Occ Analog Test

Low

 

OAnlgTst

Unocc Analog Test

Low

 

UAnlgTst

Override Value

0

 

Ovrd

Hysteresis

0.2

in H2O

Hyst

Persistence Time

0

sec

Persist

Analog Control Point

DSP

 

Name

Discrete Control Point

PNT_NAME

 

Name

Power on Delay

0

sec

PowerUp

OMNIZONE::ANCTL02: Humidity Control

 

 

 

Discrete Output Point

DEHUM

 

Name

Sensor Group/SPT Sensor

IRH

 

Name

Time Schedule

LINK_01

 

Name

Setpoint Schedule

SETPT09

 

Name

Analog

 

 

 

Hysteresis

10

%RH

Hyst

Block Iteration Rate

60

sec

BlkRate

Power on Delay

0

sec

PowerUp

OMNIZONE::CCVAV01: Modulating Economizer Control

 

 

 

Cooling Coil Valve

ECONO

 

Name

Fan Status Point

ECON_OK

 

Name

Sensor Group/SPT Sensor

VAVRESET

 

Name

Time Schedule

LINK_01

 

Name

Setpoint Schedule

SETPT02

 

Name

High Humidity Switch

SENSDI00

 

Name

Humidity Setpoint

SETPT00

 

Name

High Humidity Sensor

MAMP_I00

 

Name

VAV Setpoint Reset

 

 

 

Supply Air Setpoint

53

dF

Setpt

Reset Ratio

1

^F

RstRat

Start Reset

20

dF

StrtRst

Maximum Reset

20

^F

MaxReset

Supply Air Temperature

ECONPT

 

Name

PID_Master_Loop

 

 

 

Proportional Gain

-4

 

KP

Integral Gain

-2

 

KI

Derivative Gain

0

 

KD

Disabled Output Value

0

%

DsblOut

Minimum Output Value

0

%

MinOut

Maximum Output Value

100

%

MaxOut

Starting Value

30

%

StartVal

Block Iteration Rate

30

sec

BlkRate

Power on Delay

0

sec

PowerUp

OMNIZONE::BSP: Building Static Milliamp

 

 

 

Low Input Endpoint

4

ma

LowRange

High Input Endpoint

20

ma

HighRng

Low Conversion Endpoint

4

ma

LowConv

High Conversion Endpoint

20

ma

HighConv

Low Input Fault

4

ma

LowFlt

High Input Fault

20

ma

HighFlt

Externally Powered

No

 

ExtPower

OMNIZONE::IAQ: Indoor Air Quality

 

 

 

Low Input Endpoint

4

ma

LowRange

High Input Endpoint

20

ma

HighRng

Low Conversion Endpoint

0

 

LowConv

High Conversion Endpoint

2000

 

HighConv

Low Input Fault

4

ma

LowFlt

High Input Fault

20

ma

HighFlt

Externally Powered

Yes

 

ExtPower

OMNIZONE::CSMUX: Comp. Status MUX

 

 

 

Low Input Endpoint

0

Volts

LowRange

High Input Endpoint

11

Volts

HighRng

Low Conversion Endpoint

0

Volts

LowConv

High Conversion Endpoint

11

Volts

HighConv

Low Input Fault

1

Volts

LowFlt

High Input Fault

10.5

Volts

HighFlt

*Default values from factory.

NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

46

Page 46
Image 46
Carrier 50XJ064-104 specifications Pntname, SETPT09, SENSDI00, SETPT00, MAMPI00

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.