60
Maintenance Screens (cont)
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE::PRES:He ad Pressure(Comp1)
SystemValue 118.76 PSIG Sysvalue
Force 0Force
Status 0 HwStat
AlarmSta tus Normal AlmStat
SensorValue 118.76 PSIG SenValue
HardwareValue 1.9 Volts HwValue
ChannelNumber 24 ChanNum
ControlAlgorithm Name ADAPT02 AlgoName
AlarmAlgor ithm Name AlmName
OMNIZONE::RESET:Ext. Supply Air Reset
SystemValue 0 dF Sysvalue
Force 0Force
Status 0 HwStat
AlarmSta tus Normal AlmStat
SensorValue 0 dF SenValue
HardwareValue 1.1 Volts HwValue
ChannelNumber 20 ChanNum
ControlAlgorithm Name ADAPT01 AlgoName
AlarmAlgor ithm Name AlmName
OMNIZONE::UPDATEDB:Database Control
DatabaseError No DBError
EEPROMErro r No EEError
RAMError No RAMError
AvailableProgram Bytes 11130 EEPROM
AvailableData Bytes 14742 RAM
OMNIZONE::ALARM:C ritical Fault(Typical Discrete Out)
SystemValue Off SysVal
Force 0Force
Status 0 HwStat
AlarmSta tus Normal AlmStat
ControlValue Off CtrValue
HardwareValue Open HdwValue
ChannelNumber 16 ChanNum
ControlAlgorithm Name AlgoName
AlarmAlgor ithm Name AlmName
OMNIZONE::BP_SAFE: Bypass Acc PanelSecure (TypicalDiscrete Software)
SystemValue No Sysvalue
Force 0Force
Status 0Status
AlarmSta tus Normal AlmStat
OMNIZONE::DOPI_01:Sup ply FanStatus
DiscreteOutput Point Off Control Value
Occupied? No Status
Permiss ive Inter lock
ReferenceOutput 0 RefOut
PermInterlockFlag TRUE PIFlag
Conditional Low Condtion
ModifiedSetpoint 0.5 in H2O ModStpt
PersistenceTimer 0 sec PersTime
SetpointLimit 0.3 in H2O Value
AnalogControl Point 0.17 inH2O Value
DiscreteControl Point Off Value
TaskTimer 1 sec TaskTimr
OMNIZONE::DSALM01:Duct High Pressure (Typical Discrete Alarm)
MonitoredInput Point Off Value
ComparisonPoint Off Value
AlarmInhibit Point Off Value
AlarmStatu s Normal Status
Alarm Processor
Alarm Type 0 AlmType
Timeof Last Mess age 0:00 LastTime
Monthof Last Mess age 0 LastDate
Dayof Last Message 0 LastDate
Yearof Last Message 0 LastDate
TaskTimer 2 sec TaskTimr