Display Screens (cont)
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE:CustomConfiguration
CompressorStages 2 NUM_CMP
ResetRatio 3 dF RSET_RTO
CDWF0=NO,1=YES 0 CDFW_SWT
ECON0=NO,1=YES 0 EWT_SNS
EWTReset 0=NO,1=YES 1 EWT_RST
MOD.VLV0=NO,1=YES 0 MOD_ECON
0=CONST.,1=VARIABLE 0 FLOW_TYP
0=RAT,1=MAT,2=NONE 2 MARA _SNS
PHASE0=N O,1=YES 0 PHAS_SWT
FREEZ 0=NO,1=YES 0 FREZ_SWT
ENABLEECON. 68 dF ECON_SET
SPT0=NO,1=YES 0 SPT_SNS
PRES0=N O,1=YES 0 SPT_SNS
TWR0= NO,1=YES 0 TWR_SNS
LWT 0=NO ,1=YE S 0 LWT_S NS
IAQ0=NO,1=YES 0 IAQ_SNS
IRH0=N O,1=YES 0 IRH_SNS
BSP0=NO,1=YES 0 BSP_SNS
BSPRange 1.00 inH2O BSP_RNG
BSPLOW VALUE -0.5 in H2O BSP_LOW
Setpoints
OMNIZONE::SETPT01:Supply fan Status
OccupiedLo Setpoint 0.3 inH2O OccLow
OccupiedHi Setpoint 0.4 inH2O OccHgh
UnoccupiedLo Setpoint 0.3 in H2O UnOccLow
UnoccupiedHi Setpoint 0.4 inH2O UnOccHgh
OMNIZONE::SETPT02:VAVRESETbaseline
OccupiedLo Setpoint 0 dF OccLow
OccupiedHi Setpoint 0 dF OccHgh
UnoccupiedLo Setpoint 0 dF UnOccLow
UnoccupiedHi Setpoint 0 dF UnOccHgh
OMNIZONE::SETPT03:Heat \Cool Mode & Reset
OccupiedLo Setpoint 70 dF OccLow
OccupiedHi Setpoint 74 dF OccHgh
UnoccupiedLo Setpoint 55 dF UnOccLow
UnoccupiedHi Setpoint 85 dF UnO ccHgh
OMNIZONE::SETPT04: Head Pressure Control
OccupiedLo Setpoint 225 PSIG OccLow
OccupiedHi Setpoint 225 PSIG OccHgh
UnoccupiedLo Setpoint 225 PSIG UnOccLow
UnoccupiedHi Setpoint 225 PSIG UnOccHgh
OMNIZONE::SETPT05: Supply Static Pressure
OccupiedLo Setpoint 1.5 inH2O OccLow
OccupiedHi Setpoint 1.5 inH2O OccHgh
UnoccupiedLo Setpoint 1.5 in H2O UnOccLow
UnoccupiedHi Setpoint 1.5 inH2O UnOccHgh
OMNIZONE::SETPT06:Supply Air Temperature
OccupiedLo Setpoint 55 dF OccLow
OccupiedHi Setpoint 55 dF OccHgh
UnoccupiedLo Setpoint 55 dF UnOccLow
UnoccupiedHi Setpoint 55 dF UnO ccHgh
OMNIZONE::SETPT07:Building Static Pressure
OccupiedLo Setpoint 0.02 inH2O OccLow
OccupiedHi Setpoint 0.02 inH2O OccHgh
UnoccupiedLo Setpoint 0.02 in H2O UnOccLow
UnoccupiedHi Setpoint 0.02 inH2O UnOccHgh
OMNIZONE::SETPT08: BSP raw control
OccupiedLo Setpoint 12.32 ma OccLow
OccupiedHi Setpoint 12.32 ma OccHgh
UnoccupiedLo Setpoint 12.32 ma UnOccLow
UnoccupiedHi Setpoint 12.32 ma UnOccHgh
OMNIZONE::SETPT09:Humidit y Control
OccupiedLo Setpoint 0 %RH OccLow
OccupiedHi Setpoint 99 %RH OccHgh
UnoccupiedLo Setpoint 0 %RH UnOccLow
UnoccupiedHi Setpoint 99 %RH UnOc cHgh