48
Configuration Screens (cont)
*Defaultvalues from factory.
NOTE:See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION VALUE* UNITS NAME
OMNIZONE::HIR:Heat Interlock Relay
OutputLogic Type Normal LogType
MinimumOff Time 60 sec MinOff
MinimumOn Time 60 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::PUMP:Pump Request
OutputLogic Type Normal LogType
MinimumOff Time 5 sec MinOff
MinimumOn Time 5 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::SF:Supply Fan/VFD
OutputLogic Type Normal LogType
MinimumOff Time 30 sec MinOff
MinimumOn Time 60 sec MinOn
DelayTime 10 sec DlyTim
OMNIZONE::TOWER:Cooling Tower Request
OutputLogic Type Normal LogType
MinimumOff Time 5 sec MinOff
MinimumOn Time 5 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::TRMCT: VAVTerminals Co ntrol
OutputLogic Type Normal LogType
MinimumOff Time 60 sec MinOff
MinimumOn Time 60 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::TRMOP:VAV Terminals Open MAX
OutputLogic Type Normal LogType
MinimumOff Time 5 sec MinOff
MinimumOn Time 5 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::VENTR:Ventilation Request
OutputLogic Type Normal LogType
MinimumOff Time 3 sec MinOff
MinimumOn Time 3 sec MinOn
DelayTime 5 sec DlyTim
OMNIZONE::WARN:Non Critical Fault
OutputLogic Type Normal LogType
MinimumOff Time 4 sec MinOff
MinimumOn Time 4 sec MinOn
DelayTime 10 sec DlyTim
OMNIZONE::DSALM01:Duct High Pressure
MonitoredInput Point DHS Name
ComparisonPoint SENSDI00 Name
AlarmInhibit Point SENSDI00 Name
DiscreteCheck
AlarmLogic Normal AlmLogic
EnableDelay Time 15 sec DlyTim
PersistenceTime 10 sec Persist
Alarm Processor
AlarmP rocessing Enable AlmProc
Re-Alarm Interval 0 min ReAlmTim
Alarm=1or Alert=0 1 Type
AlarmLevel 1 AlmLevel
AlarmS ource 5 AlmSrc
AlarmRouting 11010000 AlmRtg
AlarmDes cription Index 0 AlmDesc
AlarmM essage - Part 1 Duct High Static Message
AlarmM essage - Part 2 Pressure Message
AlarmM essage - Part 3 Message
AlarmM essage - Part 4 Message
Poweron Delay 0 sec PowerUp