Carrier 50XJ064-104 specifications C4ALM, DISCRO00

Models: 50XJ064-104

1 64
Download 64 pages 22.2 Kb
Page 52
Image 52

Configuration Screens (cont)

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::DSALM11: Compressor 4 Alarm

 

 

 

Monitored Input Point

C4_ALM

 

Name

Comparison Point

SENSDI00

 

Name

Alarm Inhibit Point

SENSDI00

 

Name

Discrete Check

 

 

 

Alarm Logic

Normal

 

AlmLogic

Enable Delay Time

10

sec

DlyTim

Persistence Time

10

sec

Persist

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

2

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

0

 

AlmDesc

Alarm Message - Part 1

Compressor 4 Fau

 

Message

Alarm Message - Part 2

lt

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

OMNIZONE::DSALM12: Supply Fan Alarm

 

 

 

Monitored Input Point

SFS

 

Name

Comparison Point

SF

 

Name

Alarm Inhibit Point

SENSDI00

 

Name

Discrete Check

 

 

 

Alarm Logic

Normal

 

AlmLogic

Enable Delay Time

120

sec

DlyTim

Persistence Time

120

sec

Persist

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

2

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

0

 

AlmDesc

Alarm Message - Part 1

Check Supply Fan

 

Message

Alarm Message - Part 2

 

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

OMNIZONE::DXVAV01: Compressor Staging

 

 

 

Discrete Output Point 1

CMP1

 

Name

Discrete Output Point 2

CMP2

 

Name

Discrete Output Point 3

CMP3

 

Name

Discrete Output Point 4

CMP4

 

Name

Discrete Output Point 5

DISCRO00

 

Name

Discrete Output Point 6

DISCRO00

 

Name

Fan Status Point

COMPRES

 

Name

Sensor Group/SPT Sensor

VAVRESET

 

Name

Time Schedule

LINK_01

 

Name

Setpoint Schedule

SETPT02

 

Name

High Humidity Switch

SENSDI00

 

Name

Humidity Setpoint

SETPT00

 

Name

High Humidity Sensor

IRH

 

Name

VAV Setpoint Reset

 

 

 

Supply Air Setpoint

57

dF

SetPT

Reset Ratio

1

^F

RstRat

Start Reset

20

dF

StrtRst

Maximum Reset

20

^F

MaxReset

Supply Air Temperature

SAT

 

Name

PID_Master_Loop

 

 

 

Proportional Gain

-1

 

KP

Integral Gain

-0.4

 

KI

Derivative Gain

-0.7

 

KD

Disabled Output Value

0

%

DsblOut

Minimum Output Value

0

%

MinOut

Maximum Output Value

100

%

MaxOut

Starting Value

0

%

StartVal

Block Iteration Rate

30

sec

BlkRate

Staging Control

 

 

 

Total Number of Stages

4

 

TotalStg

On Time Delay

2

min

OnDelay

Off Time Delay

1

min

OffDelay

Power on Delay

0

sec

PowerUp

*Default values from factory.

NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

52

Page 52
Image 52
Carrier 50XJ064-104 specifications C4ALM, DISCRO00

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.