2. Press3 and then .The LID display will show:
ControllerPassword
3. Press .The LID di splay will show:
LogintoController
EnterPas sword
NOTE: The LID display has two modes: Edit mode and
Status/Maintenance mode. If the LID display is in Edit
mode, then the display will only show the word “pass-
word.”Press the keyto toggle to the Status
mode.
Pressthe todisplay:
LogintoController
EnterPas sword
4. Keyin the password and press .
NOTE: The d efault pa ssword is 1111 .
5. TheLID display will show:
LogintoController
LoggedIn
NOTE: At this point,for the 50BV unit only, the run
testwill follow th ese steps:
a. Press 37 .Thed isplay will show:
Custom Program
b. Press .The dis play will show:
2.0 Global Dictionary
OMNIZONE
c. Press (NOTE: Display will flash,
indicating that the device is now in edit mode.)
Thed isplay will show:
2.0 Global Dictionary
OMNIZONE
d. Press .The dis play will show:
CompressorStages
4.00
NOTE:A 50BV unit with only 2 compressors will
display 2.00. Skip to Step 6.
e. Input 2.00 and Press . The display will show:
CompressorStages
2.00
6. Press .The LID displaywill show:
Hardware Points
7. Press again. The L ID display will show:
SoftwarePo ints
8. Press .The LID di splay will show:
Compressor1 Status
9. Press 6times. The LID display will show:
Factory/FieldTest
Stop
10. Press1 then ,The L ID display will show:
Factory/FieldTest
Start
NOTE: At this point, the yellow warning light on the
displaypanel wil l be lit and will stay on throughout the
run test. After each successful step,the red alarm light
will blink once.
11. Thecontrol module will now check if there is input from
BYPAS(50XJ),DHS,FSD,SAT,DSP,andCSMUX.
If the control does not receive open/open/closed/
in range/in range/in range, the red alarm LED will go
onand the test will stop.
If the inputs are OK, the red alarm LED blinks once
andthe test continues.
12. Next,the control forces the Supply Fan (SF) and all of the
Compressors(COMP) off, and waits 15 seconds.
For the 50XJ unit, if the REMOTE LED and AUTO
LED on the VFD display are on, the red LED blinks
onceand the test continues.
NOTE: For the 50XJ unit, if the controller is config-
ured with a water Economizer,t he delay is 2 min. and
both valves are commanded to 0%. Bothwater valves
willclose.
13. The control forces SF on and SPEED to 20 percent and
thenwaits 30 seconds.
If the VFD display shows “10.6 Hz,” the Remote and
Auto LEDs blink, and the fan goes on, then the red LED
onthe control module blinks once and t he test continues.
NOTE: For the 50XJ unit, if the controller is config-
ured with a water Economizer the delay is 2 min. and
Econo valve is commanded to 100%. The economizer
valve will open and the RVS/HD (reverse/head
pressure)valve will remain closed.
14. The control forces SF on and SPEED to 35 percent and
thenwaits 30 seconds.
If the VFD display shows “20.0 Hz,” the Remote and
Auto LEDs blink, and the fan goes on, then the red LED
onthe control module blinks once and t he test continues.
NOTE: For the 50XJ unit, if the controller is configured
with a water Economizer the delay is 2 min. and RVS/
HDvalve is comm anded to 100%. The economizer valve
iscom manded to 0% and the RVS/HDva lve will open.
15. Thecontrol forces SFoff then waits 15 seconds.
If the VFD display shows “Off,” the Remote and Auto
LEDs are off, and the fan goes off, then the red LED on
thecontrol module blinks once andthe test continues.
NOTE:For the 50XJ unit, if the control ler isc onfigured
with a water Economizer both valves are commanded
to0%. Theeconomizer valve and RVS/HD will close.
NOTE: For the 50BV unit, the steps below (16-24)
will be completed for the number of compressors
configured.
16. The control forces CMP1 (compressor 1) on then waits
5seconds.
If CSMUXi snot in range the red LED will go on and
thet est will stop.
If CSMUX is in range, the red LED blinks once and
thet est continues.
17. Thecontrol forces CMP1 off.
18. The control forces CMP2 (compressor 2) on then waits
5seconds.
If CSMUXi snot in range the red LED will go on and
thet est will stop.
If CSMUX is in range, the red LED blinks once and
thet est continues.
19. Thecontrol forces CMP2 off.
20. The control forces CMP3 (compressor 3) on, if config-
ured,then waits 5 s econds.
If CSMUXi snot in range the red LED will go on and
thet est will stop.
If CSMUX is in range, the red LED blinks once and
thet est continues.
21. Thecontrol forces CMP3 off.