Maintenance Screens (cont)

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

OMNIZONE::ANCTL01: Supply Fan Status

 

 

 

 

 

Discrete Output Point

Off

 

 

Control

Value

Sensor Group/SPT Sensor

0.17

in H2O

 

 

Value

Occupied ?

No

 

 

 

Status

Analog

 

 

 

 

 

Low Setpoint

0.3

in H2O

 

 

LowSP

Lo Setpoint + Hyst

0

in H2O

 

 

ModLowSP

Hi Setpoint - Hyst

0

in H2O

 

 

ModHghSP

High Setpoint

0.4

in H2O

 

 

HghSP

Reference Output

FALSE

 

 

 

RefOut

Task Timer

47

sec

 

 

TaskTimr

OMNIZONE::ANCTL02: Humidity Control

 

 

 

 

 

Discrete Output Point

Off

 

 

 

Value

Sensor Group/SPT Sensor

49.56

%RH

 

 

Value

Occupied ?

No

 

 

 

Status

Analog

 

 

 

 

 

Low Setpoint

0

%RH

 

 

LowSP

Lo Setpoint + Hyst

10

%RH

 

 

ModLowSP

Hi Setpoint - Hyst

89

%RH

 

 

ModHghSP

High Setpoint

99

%RH

 

 

HghSP

Reference Output

FALSE

 

 

 

RefOut

Task Timer

25

sec

 

 

TaskTimr

OMNIZONE::BSP_IN: Building Static Pressure (Typical Analog Software point)

 

 

 

 

 

System Value

0.03

in H2O

 

 

Sysvalue

Force

0

 

 

 

Force

Status

0

 

 

 

Status

Alarm Status

Normal

 

 

 

AlmStat

OMNIZONE::CCVAV01: Modulating Economizer Control

 

 

 

 

 

Cooling Coil Valve

0

%

 

 

Value

Fan Status Point

Off

 

 

Control

Value

Sensor Group/SPT Sensor

0

dF

 

 

Value

Occupied ?

No

 

 

 

Status

High Humidity Switch

Off

 

 

 

Value

High Humidity Setpoint

99

%RH

 

 

Value

High Humidity Sensor

0

%RH

 

 

Value

VAV Setpoint Reset

 

 

 

 

 

Setpoint

73

dF

 

 

Setpoint

Setpoint Offset

20

^F

 

 

Offset

CCV Supply Air Setpoint

73

dF

 

 

CCVVRF

Supply Air Temperature

77.19

dF

 

 

Value

PID_Master_Loop

 

 

 

 

 

Reference Output

0

%

 

 

RefOut

Proportional Term

0

%

 

 

PTerm

Integral Term

0

%

 

 

ITerm

Derivative Term

0

%

 

 

DTerm

Integrator Flags

100

 

 

 

Flags

Task Timer

4

sec

 

 

TaskTimr

OMNIZONE::BSP: Building Static Milliamp

 

 

 

 

 

System Value

12.4

ma

 

 

Sysvalue

Force

0

 

 

 

Force

Status

0

 

 

 

HwStat

Alarm Status

Normal

 

 

 

AlmStat

Sensor Value

12.4

ma

 

 

SenValue

Hardware Value

12.4

ma

 

 

HwValue

Channel Number

34

 

 

 

ChanNum

Control Algorithm Name

ADAPT03

 

 

 

AlgoName

Alarm Algorithm Name

 

 

 

 

AlmName

OMNIZONE::IAQ: Indoor Air Quality

 

 

 

 

 

System Value

584.3

 

 

 

Sysvalue

Force

0

 

 

 

Force

Status

0

 

 

 

HwStat

Alarm Status

Normal

 

 

 

AlmStat

Sensor Value

584.3

 

 

 

SenValue

Hardware Value

8.7

ma

 

 

HwValue

Channel Number

36

 

 

 

ChanNum

Control Algorithm Name

 

 

 

 

AlgoName

Alarm Algorithm Name

 

 

 

 

AlmName

OMNIZONE::CSMUX: Comp. Status MUX

 

 

 

 

 

System Value

1.83

Volts

 

 

Sysvalue

Force

0

 

 

 

Force

Status

0

 

 

 

HwStat

Alarm Status

Normal

 

 

 

AlmStat

Sensor Value

1.83

Volts

 

 

SenValue

Hardware Value

1.8

Volts

 

 

HwValue

Channel Number

3

 

 

 

ChanNum

Control Algorithm Name

 

 

 

 

AlgoName

Alarm Algorithm Name

LMALM03

 

 

 

AlmName

59

Page 59
Image 59
Carrier 50XJ064-104 specifications False, Ccvvrf, ADAPT03, LMALM03

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.