Configuration Screens (cont)

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::INTLK09: Condenser Pump

 

 

 

Discrete Output Point

PUMP

 

Name

Discrete Input Point 1

COOLOK

 

Name

Discrete Input Point 2

SENSDI00

 

Name

Discrete Interlock

 

 

 

Input 1 Comparison

On

 

Sns1Sta

Input 2 Comparison

Off

 

Sns2Sta

Off Persistence Time

30

sec

OffPrst

On Persistence Time

2

sec

OnPrst

Output Logic Type

Normal

 

LogType

Power on Delay

0

sec

PowerUp

OMNIZONE::INTLK10: Tower Request

 

 

 

Discrete Output Point

TOWER

 

Name

Discrete Input Point 1

COOLOK

 

Name

Discrete Input Point 2

SENSDI00

 

Name

Discrete Interlock

 

 

 

Input 1 Comparison

On

 

Sns1Sta

Input 2 Comparison

Off

 

Sns2Sta

Off Persistence Time

30

sec

OffPrst

On Persistence Time

2

sec

OnPrst

Output Logic Type

Normal

 

LogType

Power on Delay

0

sec

PowerUp

OMNIZONE::INTLK11: Compressor Cooling

 

 

 

Discrete Output Point

COMPRES

 

Name

Discrete Input Point 1

COOLOK

 

Name

Discrete Input Point 2

FAN_CDWF

 

Name

Discrete Interlock

 

 

 

Input 1 Comparison

On

 

Sns1Sta

Input 2 Comparison

On

 

Sns2Sta

Off Persistence Time

2

sec

OffPrst

On Persistence Time

30

sec

OnPrst

Output Logic Type

Normal

 

LogType

Power on Delay

0

sec

PowerUp

OMNIZONE::LINK_01: Linkage/AOSS Schedule 01

 

 

 

Setpoint Bias

VOLT_I00

 

Name

Setpoint Schedule

SETPT03

 

Name

Adaptive Optimal Start

 

 

 

AO Start Enable

Disable

 

Enable

Building Insulation

30

 

BldInsul

Unoccupied 24hr Factor

15

 

UnOccFct

Offset Low Value

0

^F

Value

Offset High Value

0

^F

Value

Sensor Group/SPT Sensor

CTRLPT

 

Name

Time Schedule

OCCPC01

 

Name

Outside Air Temp

OAT

 

Name

NTFC Algorithm

NTFC_00

 

Name

Heating Algorithm

HCVAV01

 

Name

Supply Air Temp

SAT

 

Name

Fan Status

SF_SFS

 

Name

Adaptive Optimal Stop

 

 

 

AO Stop Enable

Disable

 

Enable

Maximum Stop Time

60

min

MaxStop

Setpoint Bias

2

^F

SPBias

Power on Delay

0

sec

PowerUp

Evacuation

EVAC

 

Evacuate

Pressurization

TRMOP

 

Pressure

OMNIZONE::LMALM01: Supply air Sensor

 

 

 

Monitored Input Point

SAT

 

Name

Alarm Inhibit Point

SENSDI00

 

Name

Limit Check

 

 

 

Low Limit

25

dF

LowLim

High Limit

150

dF

HighLim

Enable Delay Time

15

sec

DlyTim

Persistence Time

10

sec

Persist

Hysteresis

5

^F

Hyst

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

1

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

7

 

AlmDesc

Alarm Message - Part 1

 

 

Message

Alarm Message - Part 2

 

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

*Default values from factory.

NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

55

Page 55
Image 55
Carrier 50XJ064-104 specifications VOLTI00, SETPT03, NTFC00, HCVAV01

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.