43
APPENDIX B — CONTROL SCREENSDisplay Screens
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE::HWP01-32:Hardwarepoints Table 1
SupplyAir Temperature 67 dF SAT
DuctStatic Pressure 0.2 inH2O DSP
Comp.Status MUX 1.86 Volts CSMUX
FireAlarm /Shut Down Enable FSD
Cond.Water Flow Switch Yes CDWF
RemoteOccupancy Disable ROCC
DuctHigh Press. Switch Normal DHS
EnteringWater Temp. 69.9 dF EWT
Compressor1 Relay Stop CMP1
Compressor2 Relay Stop CMP2
Compressor3 Relay Stop CMP3
Compressor4 Relay Stop CMP4
SupplyFan/VFD Stop SF
VFDSpeed Signal 0 % SPEED
NonCritical Fault Off WARN
CriticalFault Off ALARM
Mixed/ReturnAir Temp 77.2 dF MA_RA
DirtyF ilterS tatus Clean FLTS
PhaseLoss Prot ection N ormal PHASE
Ext.Supply Air Res et 0 dF RESET
WaterEcon. FreezeStat Normal FREEZ
Space_ResetSensor 79.2 dF SPT
VFDBypass Enable Disable BYPAS
HeadPressure(Comp1) 118.76 PSIG PRES
VentilationRequest Close VENTR
VAVTerminalsCont rol No TRMCT
2-position/EconoValve 0 % ECONO
Reverse/HeadPress Ctrl 100 % Control MVLV
HotWater Valve 0 % H WV
HeatInterlock Relay Off HIR
BypassStar t_Stop Stop BPS_S
VAVTerminals Open MAX Close TRMOP
OMNIZONE::HWP33-64:Hardware points t able2
CoolingTower Sump Temp. 57.5 dF TWR
BuildingStatic Milliamp 12.51 ma BSP
CondenserLeaving Water 70.3 dF LWT
IndoorAir Quality 587.21 IAQ
IndoorRelative Humidity 49. 7 % IRH
OutdoorAir Temp. 76.1 dF OAT
HeatStage 1 Off HEAT1
HeatStage 2 Off HEAT2
HeatStage 3 Off HEAT3
HeatStage 4 Off HEAT4
PumpRequest Off PUMP
CoolingTower Request Off TOWER
ExhaustFan 0 % EXH
Ext.Dehumidification Stop DEHUM
OMNIZONE::SWP65-96:Software Points
Compressor1 Status Off CLO1
Compressor2 Status Off CLO2
Compressor3 Status Off CLO3
Compressor4 Status Off CLO4
BypassAcc Panel Secure No BP_SAFE
DXVAV RESET Control 0 dF VAVRESET
Factory/FieldTest Stop FLDTST
BuildingStatic Pressure 0.03 in H2O BSP_IN
TimeClock Off TIMCLOCK
Cooling Disable COOLOK
SupplyFan Status Off Control SFS
Okto run Fan No OKFAN
OKFan + Sup. Fan Stat FALSE SF_SFS
Fan+ Cond. Water Flow FALSE FAN_CDWF
EquipmentMode Cool Control MODE
ActivateEvacuation Mode Disable EVAC
SpaceControl Point 74 dF CTRLPT
Mod.Econ Enabled No Control ECON_OK
HeadPressure Control Disable Control HEAD
EconomizerControl Temp. 77.22 dF ECONPT
CompressorCooling Disable COMPRES
DuctStatic Failure Normal DSP_ALM
Compressor1 Alar m Normal C1_ALM
Compressor2 Alar m Normal C2_ALM
Compressor3 Alar m Normal C3_ALM
Compressor4 Alar m Normal C4_ALM
Cond.Flow Alarm Status Disable Control CDWF_ST