Table 16 — Trip Messages for 50BV VFD (cont)

ERROR

COMMUNICATION

PROBLEM

POSSIBLE CAUSES

REMEDIES

CODE

NO.

 

 

 

*UC

1D

Small-current

• The output current falls to the low-current

• Enable F610 (low-current detection

 

 

operation trip

detection level during operation.

parameter).

 

 

 

 

• Check whether the detection level is set

 

 

 

 

properly to the system.

 

 

 

 

(F611 and F612)

 

 

 

 

• If no error is found in the setting, make a

 

 

 

 

service call.

EF2

22h

Ground fault trip

• A ground fault occurs in the output cable

• Check the cable and the motor for ground

 

 

 

or the motor.

faults.

E

11h

Emergency stop

• During automatic operation or remote

• Reset the inverter.

 

 

 

operation, a stop command is entered from

 

 

 

 

the operation panel or a remote input device.

 

Err2

15h

Main unit RAM fault

• The control RAM is defective.

• Make a service call.

Err3

16h

Main unit ROM fault

• The control ROM is defective.

• Make a service call.

Err4

17h

CPU fault trip

• The control CPU is defective.

• Make a service call.

Err5

18h

Remote control

• An error arises during remote operation.

• Check the remote control device,

 

 

error

 

cables, etc.

EtYP

29h

Inverter type error

• The control circuit board (main circuit

• Make a service call.

 

 

 

board or drive circuit board) is replaced.

 

EEP1

12h

EEPROM fault

• A data writing error occurs.

• Turn off the inverter, then turn it on again.

 

 

 

 

If it does not recover from the error, make

 

 

 

 

a service call.

Etn

28h

Auto-tuning error

• Check the settings of the motor parameters F401to F408

 

 

 

• Check that the motor is not two or more sizes smaller in capacity than the inverter.

 

 

 

• Check that the inverter output cable is not too thin.

 

 

 

• Check that the motor is not running.

 

 

 

 

• Check that the motor is a three-phase inductive motor.

*With a parameter, you can choose between trip-on and -off.

NOTES:

1.During operation, the following alarms may be displayed, which have the same meaning as previously defined alarms.

C (overcurrent alarm) — same as OC

P (overvoltage alarm) — same as OP

L (overload alarm) — same as OL1/OL2

H (overheat alarm) — same as OH

2.If two or more problems arise simultaneously, one of the following alarms appears and blinks. CP, PL, CPL

The blinking alarms, C, P, L, H are displayed in this order from left to right.

26

Page 26
Image 26
Carrier 50XJ064-104 specifications Error Communication Problem Possible Causes Remedies Code, EF2

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.