9
Pressing the appropriate LID numeric key (i.e., 2) and
the appropriate function key (i.e., ) to directly
access an item without having to scroll through all the
items in that category.Press to display the first
maintenancedecision.
EditMode — Because the LID first displays items in Status
mode when it is powered up, the user must log on to the con-
nected CC6400 Controller and press the key to
switchto Edit mode.
While in Edit mode, the user can change the configuration
ofitems. For example, the user could cha nge the value of an al-
gorithm’sconfiguration decision.
NOTE: Not all items have configuration data. If the item
selected does not have configuration data, pressing the
key will have no effect. The LID will display
“Noconfiguration.”
AccessingItems in Edit Mode — The two ways to access
items in Edit mode are the same as in Status mode, except for
anadditional step — pre ssing the key.
The user can access configuration data in Edit mode in two
ways:
Pressingthe appropriate function key (i.e., ) once
to access a category (i.e., alarms), pressing
and then continuing to press that key ( ) to scroll
through all the items in that category (i.e., Limit Alarm,
Set point Alarm, Discrete Alarm, First Out Alarm,
Runtime Alarm, and Number of StartsA larm).
NOTE: Scrolling by repeatedly pressing the function key
displays the name of all the items in that category, whether
or not they are actually configured. Scrolling by pressing
the up or down arrow displays only theconfi gured items
within that category.
Pressing the appropriate LID numeric key (i.e., 2),
the appropriate function key (i.e., ), and
to directly access an item without having
tos croll through all the items in that category.
QUICK ACCESS IN EITHER STATUS OR EDIT
MODE —Use Table 6 as a reference to directly access
CC6400 Controller items using a LID in either Status or Edit
mods. For example, to access maintenance data for the AO —
Heating VAValgorithm, press , , and . To
access configuration data for the AO (Analog Output) —
Heating VAValgorithm, press , , ,
and .Ifthe database consisted of two AO — Heating
VAV algorithms, to access the second one, press , (deci-
mal), ,, ,and .
ALRM
ENTER
EXPN/EDIT
EXPN/EDIT
EXPN/EDIT
ALRM
EXPN/EDIT
ALRM
ALRM
EXPN/EDIT
6ALGO ENTER
6ALGO EXPN/EDIT
ENTER
6 .
2ALGO EXPN/EDIT ENTER
Fig. 5 — Local Interface Display (LID)
ENTER
CLEAR
SRVC
HIST ALGO
TEST
ALRM
3
6
9
12
45
78
0.
STAT
SET SCHD
EXPN
EDIT
FUNCTION
KEYS
OPERATIVE
KEYS
FUNCTION
KEYS
OPERATIVE
KEYS
NUMERICKEYS
OMNIZONE VPAC12:00 02-06-04