56
Configuration Screens (cont)
*Defaultvalues from factory.
NOTE:See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION VALUE* UNITS NAME
OMNIZONE::LMALM02: Entering WaterTemp.
MonitoredInput Point EWT Name
AlarmI nhibitPoint SENSDI00 Name
LimitCheck
LowLimit 35 dF LowLim
HighLimit 95 dF HighLim
EnableDelay Time 15 sec DlyTim
PersistenceTime 10 sec Persist
Hysteresis 5 ^F Hyst
AlarmP rocessor
AlarmProc essing Enable AlmProc
Re-AlarmInter val 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
AlarmLevel 1 AlmLevel
AlarmSourc e 5 AlmSrc
AlarmRouting 11010000 AlmRtg
AlarmD escription Index 7 AlmDesc
AlarmMes sage - Part 1 Message
AlarmMes sage - Part 2 Message
AlarmMes sage - Part 3 Message
AlarmMes sage - Part 4 Message
Poweron Delay 0 sec PowerUp
OMNIZONE::LMALM03: Compressor Mux
MonitoredInput Point CSMUX Name
AlarmI nhibitPoint SENSDI00 Name
LimitCheck
LowLimit 1.5 Volts LowLim
HighLimit 9.9 Volts HighLim
EnableDelay Time 15 sec DlyTim
PersistenceTime 10 sec Persist
Hysteresis 0.2 Volts Hyst
AlarmP rocessor
AlarmProc essing Enable AlmProc
Re-AlarmInter val 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
AlarmLevel 1 AlmLevel
AlarmSourc e 5 AlmSrc
AlarmRouting 11010000 AlmRtg
AlarmD escription Index 7 AlmDesc
AlarmMes sage - Part 1 Message
AlarmMes sage - Part 2 Message
AlarmMes sage - Part 3 Message
AlarmMes sage - Part 4 Message
Poweron Delay 0 sec PowerUp
OMNIZONE::LMALM04:Mixed/Return Air
MonitoredInput Point MA_RA Name
AlarmI nhibitPoint SENSDI00 Name
LimitCheck
LowLimit 35 dF LowLim
HighLimit 120 dF HighLim
EnableDelay Time 10 sec DlyTim
PersistenceTime 10 sec Persist
Hysteresis 5 ^F Hyst
AlarmP rocessor
AlarmProc essing Enable AlmProc
Re-AlarmInter val 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
AlarmLevel 2 AlmLevel
AlarmSourc e 5 AlmSrc
AlarmRouting 11010000 AlmRtg
AlarmD escription Index 7 AlmDesc
AlarmMes sage - Part 1 Message
AlarmMes sage - Part 2 Message
AlarmMes sage - Part 3 Message
AlarmMes sage - Part 4 Message
Poweron Delay 0 sec PowerUp