Carrier 50XJ064-104 specifications Non-Trip Messages for the 50BV VFD, Trip Messages for 50BV VFD

Models: 50XJ064-104

1 64
Download 64 pages 22.2 Kb
Page 24
Image 24

Table 15 — Non-Trip Messages for the 50BV VFD

ERROR

PROBLEM

POSSIBLE CAUSES

REMEDIES

CODE

 

 

 

OFF (Note 1)

ST terminal OFF

• The ST-CC circuit is opened.

• Close the ST-CC circuit.

NOFF

Undervoltage in main

• The supply voltage between R, S and T is

• Measure the main circuit supply voltage.

 

circuit

under voltage.

If the voltage is at a normal level, the

 

 

 

inverter requires repairing.

rtrY

Retry in process

• The inverter is in the process of retry.

• The inverter is normal if it restarts after

 

 

• A momentary stop occurred.

several tens of seconds.

 

 

 

The inverter restarts automatically. Be careful of the

 

 

 

machine because it may suddenly restart.

Err1

Frequency point

• The frequency setting signals at points 1

• Set the frequency setting signals at points

 

setting error

and 2 are set too close to each other.

1 and 2 apart from each other.

CLr

Clear command

• This message is displayed when pressing

• Press the STOP key again to clear the

 

acceptable

the STOP key while an error code is displayed.

trip.

EOFF

Emergency stop

• The operation panel is used to stop the

• Press the STOP key for an emergency stop.

 

command acceptable

operation in automatic control or remote

To cancel the emergency stop, press any other key.

 

 

control mode.

 

HI/LO

Setting error alarm /

• An error is found in a setting when data is

• Check whether the setting is made

 

An error code and

reading or writing.

correctly.

 

data are displayed

 

 

 

alternately twice each.

 

 

db

DC braking

• DC braking in process

• Normal if the message disappears after

 

 

 

several tens of seconds. (See Note 2.)

In It

Parameters in the

• Parameters are being initialized to default

• Normal if the message disappears after a

 

process of initialization

values.

while (several seconds to several tens of seconds).

 

Setup parameters in

• Setup parameters are in the process of

• Normal if the message disappears after a

 

the process of being set

being set.

while (several seconds to several tens of seconds).

Atn

Auto-tuning in process

Auto-tuning is in process.

• Normal if the message disappears after

 

 

 

several seconds.

NOTES:

1.ST : Terminal of stand by function.

2.When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter, you can judge the inverter to be normal if “db” disappears when opening the circuit between the terminal and CC.

Table 16 — Trip Messages for 50BV VFD

ERROR

COMMUNICATION

PROBLEM

POSSIBLE CAUSES

REMEDIES

CODE

NO.

 

 

 

OC1

1

Overcurrent during

• The acceleration time ACC is too short.

• Increase the acceleration time ACC.

 

 

acceleration

• The V/F setting is improper.

• Check the V/F parameter.

 

 

 

• A restart signal is input to the rotating

• Use F301 (auto-restart) and F302

 

 

 

motor after a momentary stop, etc.

(ride-through control).

 

 

 

• A special motor (e.g. motor with a small

• Increase the carrier frequency F300.

 

 

 

impedance) is used.

 

OC2

2

Overcurrent during

• The deceleration time dEC is too short.

• Increase the deceleration time dEC.

 

 

deceleration

(During deceleration)

 

OC3

3

Overcurrent during

• The load fluctuates abruptly.

• Reduce the load fluctuation.

 

 

operation

• The load is in an abnormal condition.

• Check the load (operated machine).

OCR

5

Arm overcurrent at

• A main circuit element is defective.

• Make a service call.

 

 

start-up

 

 

OCL

4

Overcurrent (An

• The insulation of the output main circuit or

• Check the cables and wires for defective

 

 

overcurrent on the

motor is defective.

insulation.

 

 

load side at start-up)

• The motor has too small impedance.

 

OP1

A

Overvoltage during

• The input voltage fluctuates abnormally.

• Insert a suitable input reactor.

 

 

acceleration

(1) The power supply has a capacity of

 

 

 

 

200kVA or more.

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

opened or closed.

 

 

 

 

(3) A system using a thyristor is connected

 

 

 

 

to the same power distribution line.

 

 

 

 

• A restart signal is input to the rotating

• Use F301 (auto-restart) and F302

 

 

 

motor after a momentary stop, etc.

(ride-through control).

OP2

B

Overvoltage during

• The deceleration time dEC is too short.

• Increase the deceleration time dEC.

 

 

deceleration

(Regenerative energy is too large.)

• Install a suitable dynamic braking resistor.

 

 

 

• F304 (dynamic braking resistor

• Enable F304 (dynamic braking selection).

 

 

 

activation) is off.

• Enable F305 (overvoltage limit operation).

 

 

 

• F305 (overvoltage limit operation) is off.

• Insert a suitable input reactor.

 

 

 

(1) The input voltage fluctuates abnormally.

 

 

 

 

The power supply has a capacity of

 

 

 

 

200kVA or more.

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

opened or closed.

 

 

 

 

(3) A system using a thyristor is connected

 

 

 

 

to the same power distribution line.

 

24

Page 24
Image 24
Carrier 50XJ064-104 specifications Non-Trip Messages for the 50BV VFD, Trip Messages for 50BV VFD

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.