Chapter 2 Installation

Page 2 - 4

 

Installation Procedure

Step 5.

Set Array

Input Voltage

Switch

Step 6.

Attach Power

Cord

Step 7.

Power Up the

Array

Step 8.

Check Array

Status

Before you connect the array’s power cord to an AC outlet, you must set the array power supply’s input voltage selection switch to the proper position: the “115” setting for 100-120 VAC, or the “230” setting for 200-240 VAC.

The power supply’s input voltage selection switch is located between the two power cord connectors on the rear panel of the array.

Caution If the input voltage selection switch is not in the correct position, the array power supply will be damaged when power is applied.

First, verify that the array power ON/OFF switch on the rear panel of the enclosure is in the OFF position. Then plug the power cord into the appropriate connector on the rear panel of the array. Plug the other end of the power cable into the power source.

Caution The standard power cord provided with the array is for use in the United States and Canada. If necessary, replace the power cord with one that meets local safety and electrical standards.

Move the power switch on the rear panel of the array enclosure to the ON position.

Observe the display/operation panel for the following start-up displays and status indications.

Drive Status

At array reset or power-up, the display/operation panel will cycle through a series of displays that show the status of each drive in the array.

Drives in the array are numbered from right to left, with drive number 1 representing the parity drive and drives 2-9 representing the eight data drives.

9 8 7 6 - 5 4 3 2 - 1

(Drive 1 = Parity Drive)