2-6Compaq 3000 Series UPS Operation and Reference Guide

Use this procedure to activate the REPO port:

1.Install a suitable switch at the required remote location.

2.Remove the connector block from the REPO port.

REMOTE

POWER OFF

Figure 2-2. Removing the connector block

3.Wire the connector block using stranded, non-shielded wire (AWG #22 - #18, or equivalent).

4.Replace the connector block in the REPO port.

REMOTE

POWER OFF

Figure 2-3. Replacing the connector block

IMPORTANT: The remote switch must be in the OFF (open) position to enable power to the output receptacles.

Page 28
Image 28
Compaq 3000 Series manual Removing the connector block