C-6Compaq 3000 Series UPS Operation and Reference Guide

Battery Runtime

 

 

 

Table C-7

 

Estimated Battery Runtime

 

 

 

 

Load (VA)

 

 

Battery Runtime (Minutes)

700

80

 

 

 

800

56

 

 

900

50

 

 

1000

45

 

 

1200

38

 

 

1400

32

 

 

1500

30

 

 

1800

21

 

 

2000

19

 

 

2200

17

 

 

2400

14

 

 

3000

11

 

 

 

 

If a device list the power in Watts, use the following conversion equation:

Volts x Amps = VA per device

If only Watts are given:

Watts x 1.35 = VA