Operation 3-11

Initiating a Self-test

To initiate a self-test, press the TEST/ALARM RESET button and hold for three seconds. The UPS acknowledges compliance with five beeps.

1

Figure13-4. The TEST/ALARM RESET button

TEST/ALARM RESET button

IMPORTANT: A portion of the self-test requires battery power; the self-test cannot be initiated if the batteries are less than 90% charged.

During the self-test, it is normal for the UPS to turn on individual LEDs momentarily; however, if an alarm condition is detected, the UPS will turn on the appropriate LED and may sound an audio alarm.

WARNING: To reduce the risk of electric shock from earth conductor leakage current, use the self-test procedure to check the UPS batteries (rather than unplugging the UPS).

For the meaning of individual LEDs, see “Front Panel LEDs in the Standby and Operate Modes,” in this chapter.

For information on what to do if the self-test detects a problem, see Chapter 6, “Troubleshooting.”