Compaq 3000 Series manual Site Wiring Fault LED, Battery Charge LEDs, Battery Service LED

Models: 3000 Series

1 96
Download 96 pages 21.07 Kb
Page 39
Image 39

3-6Compaq 3000 Series UPS Operation and Reference Guide

Site Wiring Fault (LED 5)

 

 

 

 

Table 3-2

 

 

 

 

Site Wiring Fault LED

 

 

 

 

 

LED

 

Color

 

Meaning

 

 

 

 

 

5

 

Red

 

No ground connection between utility power and the UPS.

 

 

 

 

 

 

 

 

 

The line and neutral connections between utility power and the

 

 

 

 

UPS are reversed.

 

 

 

 

 

 

 

 

 

The UPS voltage configuration may be incorrect.

 

 

 

 

 

Note: For units factory-configured for 208V, the Site Wiring Fault function has been disabled. If reconfiguring a 230V unit to operate at 208V, the Site Wiring Fault function must be manually disabled. See the section “Changing Configuration Parameters” in Chapter 4, “Configuration.”

Battery Charge (LEDs 6-9)

 

 

 

 

Table 3-3

 

 

 

 

Battery Charge LEDs

 

 

 

 

 

LED

 

Color

 

Meaning

 

 

 

 

 

6

 

Green

 

Batteries are between 67% and 100% charged.

 

 

 

 

(LEDs 7 and 8 are also green)

 

 

 

 

 

7

 

Green

 

Batteries are approximately 66% charged.

 

 

 

 

(LED 8 is also green)

 

 

 

 

 

8

 

Green

 

Batteries are approximately 33% charged.

 

 

 

 

 

9

 

Red

 

Batteries are low; approximately three to five minutes of battery

 

 

 

 

backup remain.

 

 

 

 

 

Battery Service (LED 10)

 

 

 

 

Table 3-4

 

 

 

 

Battery Service LED

 

 

 

 

 

LED

 

Color

 

Meaning

 

 

 

 

 

10

 

Red

 

Potential battery failure.

 

 

 

 

 

Note: When LED 10 is red, the audio alarm will sound, indicating the UPS has detected a potential battery failure. The UPS batteries may need to be replaced in 30 to 60 days.

Page 39
Image 39
Compaq 3000 Series manual Site Wiring Fault LED, Battery Charge LEDs, Battery Service LED